Section 3: System Configuration
3.2.8 Example 7 - Parallel System – 7"WC – Hybrid
Figure 3-15 below shows the same house and similar piping system as Example 2. e piping is arranged in parallel fashion,
with individual CSST appliance runs supplied by a main distribution manifold. e main trunk line (“A”) from the meter
to the distribution manifold is rigid pipe rather than CSST. e utility companys supply pressure (downstream of the meter)
is 7"WC. e utility company advises that the specific gravity of the gas delivered will be 0.60 and the energy content is 1
CFH = 1000 BTUH.
e allowable pressure drop across the system has been determined to be 2"WC (supply pressure 7"WC - appliance
requirement 5"WC). 0.5"WC pressure drop will be taken over the rigid pipe trunk line and the remaining appliance runs.
Note: Rigid pipe sized using a 0.5"WC pressure drop table, as no 2.0"WC pressure drop table for Rigid pipe is available.
Table 3-8
Section Description Load Delivered by Section Section Length Run Length Tube Size
A” – Rigid Trunk 221 CFH = 221,000 BTUH 45 feet 70feet 1" Rigid
“B” – Furnace 80 CFH = 80,000 BTUH 15 feet 60 feet 3/4" CSST
“C” – Water Heater 36 CFH = 36,000 BTUH 10 feet 55 feet 1/2" CSST
“D” – Range 52 CFH = 52,000 BTUH 20 feet 65 feet 1/2" CSST
“E” – Dryer/BBQ Trunk 53 CFH = 53,000 BTUH 20 feet 70 feet 1/2" CSST
“F” – Dryer 28 CFH = 28,000 BTUH 5 feet 70 feet 1/2" CSST
“G” – BBQ 25 CFH = 25,000 BTUH 5 feet 70 feet 1/2" CSST
Run Length for Trunk Sections = Distance from meter to furthest appliance (Longest Run)
Run Length for Appliance Sections = Distance from meter to each appliance
SIZING RUN “A”
Run “A” is sized by the total load of all appliances and the run length from the meter to the furthest appliance
e total load of all appliances is 80 + 36 + 52 + 28 + 25 = 221CFH
e run length to the BBQ (furthest appliance) is 45 + 20 + 5 = 70ft
Referring to Table 7-23 (Rigid pipe 0.5"WC pressure drop): for a 70ft run, 1" pipe has a capacity over 221CFH (actual: 240)
SIZING RUN “B”
Run “B” is sized by the load of the supplied appliance and the run length from the meter to the supplied appliance
e load of the furnace is 80CFH
e run length to the furnace is 45 + 15 = 60ft
Referring to Table 7-4 (2.0"WC pressure drop) for a 60ft run, 3/4" CSST has a capacity over 80CFH (actual: 152)
Fig. 3-15