SIZING RUN “E”
• Run “E” is sized by the load of all supplied appliances and the run length from the meter to the farthest regulator
• e total load of all appliances is 28 + 25 = 53CFH
• e run length to the farthest regulator is 45 + 20 = 65ft
• Referring to Table 7-10 (2 PSI with a 1 PSI drop): for a 70-ft run, 3/8" CSST has a capacity over 53CFH (97 actual)
NOTE: Gastite® recommends that trunk lines be 1/2" minimum. erefore, this trunk run should be upsized to 1/2".