Section 3: System Configuration
3.2.4 Example 3 - Parallel System – 12-14"WC
Figure 3-11 below shows the same house and piping system as Example 2. e piping is arranged in parallel fashion,
with individual CSST appliance runs supplied by a main distribution manifold. e utility company’s supply pressure
(downstream of the meter) is 12-14"WC. e utility company advises that the specific gravity of the gas delivered will be
0.60 and the energy content is 1 CFH = 1000 BTUH. e allowable pressure drop across the system has been determined
to be 7"WC (supply pressure 12"WC - appliance requirement 5"WC). As there is no 7"WC pressure drop chart available
we must use the next lowest chart: in this case the 6"WC pressure drop chart (Table 7-8).
Table 3-4
Section Description Load Delivered by Section Section Length Run Length Tube Size
“A” – Trunk 221 CFH = 221,000 BTUH 45 feet 70 feet 3/4" CSST
“B” – Furnace 80 CFH = 80,000 BTUH 15 feet 60 feet 1/2" CSST
“C” – Water Heater 36 CFH = 36,000 BTUH 10 feet 55 feet 3/8" CSST
“D” – Range 52 CFH = 52,000 BTUH 20 feet 65 feet 1/2" CSST
“E” – Dryer/BBQ Trunk 53 CFH = 53,000 BTUH 20 feet 70 feet 1/2" CSST
“F” – Dryer 28 CFH = 28,000 BTUH 5 feet 70 feet 3/8" CSST
“G” – BBQ 25 CFH = 25,000 BTUH 5 feet 70 feet 3/8" CSST
Run Length for Trunk Sections = Distance from meter to furthest appliance (Longest Run)
Run Length for Appliance Sections = Distance from meter to each appliance
SIZING RUN “A”
• Run “A” is sized by the total load of all appliances and the run length from the meter to the furthest appliance
• e total load of all appliances is 80 + 36 + 52 + 28 + 25 = 221CFH
• e run length to the BBQ (furthest appliance) is 45 + 20 + 5 = 70ft
• Referring to Table 7-8 (6.0"WC pressure drop) for a 70ft run, 3/4" CSST has a capacity over 221CFH (actual: 234)
SIZING RUN “B”
• Run “B” is sized by the load of the supplied appliance and the run length from the meter to the supplied appliance
• e load of the furnace is 80CFH
• e run length to the furnace is 45 + 15 = 60ft
• Referring to Table 7-8 (6.0"WC pressure drop) for a 60ft run, 1/2" CSST has a capacity over 80CFH (actual: 131)