Section 3: System Configuration
3.2.4 Example 3 - Parallel System – 12-14"WC
Figure 3-11 below shows the same house and piping system as Example 2. e piping is arranged in parallel fashion,
with individual CSST appliance runs supplied by a main distribution manifold. e utility companys supply pressure
(downstream of the meter) is 12-14"WC. e utility company advises that the specific gravity of the gas delivered will be
0.60 and the energy content is 1 CFH = 1000 BTUH. e allowable pressure drop across the system has been determined
to be 7"WC (supply pressure 12"WC - appliance requirement 5"WC). As there is no 7"WC pressure drop chart available
we must use the next lowest chart: in this case the 6"WC pressure drop chart (Table 7-8).
Table 3-4
Section Description Load Delivered by Section Section Length Run Length Tube Size
A” – Trunk 221 CFH = 221,000 BTUH 45 feet 70 feet 3/4" CSST
“B” – Furnace 80 CFH = 80,000 BTUH 15 feet 60 feet 1/2" CSST
“C” – Water Heater 36 CFH = 36,000 BTUH 10 feet 55 feet 3/8" CSST
“D” – Range 52 CFH = 52,000 BTUH 20 feet 65 feet 1/2" CSST
“E” – Dryer/BBQ Trunk 53 CFH = 53,000 BTUH 20 feet 70 feet 1/2" CSST
“F” – Dryer 28 CFH = 28,000 BTUH 5 feet 70 feet 3/8" CSST
“G” – BBQ 25 CFH = 25,000 BTUH 5 feet 70 feet 3/8" CSST
Run Length for Trunk Sections = Distance from meter to furthest appliance (Longest Run)
Run Length for Appliance Sections = Distance from meter to each appliance
SIZING RUN “A”
Run “A” is sized by the total load of all appliances and the run length from the meter to the furthest appliance
e total load of all appliances is 80 + 36 + 52 + 28 + 25 = 221CFH
e run length to the BBQ (furthest appliance) is 45 + 20 + 5 = 70ft
Referring to Table 7-8 (6.0"WC pressure drop) for a 70ft run, 3/4" CSST has a capacity over 221CFH (actual: 234)
SIZING RUN “B”
Run “B” is sized by the load of the supplied appliance and the run length from the meter to the supplied appliance
e load of the furnace is 80CFH
e run length to the furnace is 45 + 15 = 60ft
Referring to Table 7-8 (6.0"WC pressure drop) for a 60ft run, 1/2" CSST has a capacity over 80CFH (actual: 131)
Fig. 3-11