Section 7: Sizing Tables and Pressure Drop Charts
Table 7-7
Maximum Capacity of FlashShield™ Flexible Gas Piping in Cubic Feet Per Hour of Natural Gas
with a Gas Pressure of 0.5 PSI or Less and a Pressure Drop of 5.0"WC
(based on a 0.60 specific gravity gas)
Tubing Tubing Length (ft)
EHD Size 5 10 15 20 25 30 40 50 60 70 80 90 100 125 150
13 3/8" 157 109 88 76 67 61 52 47 42 39 36 34 32 29 26
18 1/2" 409 290 238 206 185 169 146 131 120 111 104 98 93 83 76
23 3/4" 723 526 437 383 345 318 278 251 231 215 202 192 183 165 152
31 1" 1749 1254 1032 898 807 739 644 578 530 492 461 436 415 372 341
37 1-1/4" 2694 1918 1572 1365 1224 1119 972 871 797 739 692 653 620 556 508
48 1-1/2" 5704 4054 3320 2881 2581 2359 2048 1834 1677 1554 1455 1373 1304 1168 1068
60 2" 12692 8880 7205 6213 5538 5041 4346 3874 3527 3257 3041 2862 2711 2416 2199
Tubing Tubing Length (ft)
EHD Size 200 250 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
13 3/8" 22 20 18 15 14 13 12 11 10 10 9 9 8 8 8
18 1/2" 66 59 54 47 42 38 36 33 32 30 29 27 26 25 24
23 3/4" 133 120 110 97 87 80 75 70 67 63 61 58 56 54 53
31 1" 297 267 244 213 191 175 163 153 144 137 131 126 121 117 113
37 1-1/4" 441 396 362 314 282 258 239 224 211 201 191 183 176 170 164
48 1-1/2" 926 830 759 658 590 539 500 468 442 419 400 383 368 355 343
60 2" 1896 1690 1539 1327 1183 1077 994 928 874 827 788 753 723 696 671
Table 7-8
Maximum Capacity of FlashShield™ Flexible Gas Piping in Cubic Feet Per Hour of Natural Gas
with a Gas Pressure of 0.5 PSI or Less and a Pressure Drop of 6.0"WC
(based on a 0.60 specific gravity gas)
Tubing Tubing Length (ft)
EHD Size 5 10 15 20 25 30 40 50 60 70 80 90 100 125 150
13 3/8" 173 120 97 83 74 67 58 51 47 43 40 38 36 32 29
18 1/2" 447 318 260 226 202 185 160 144 131 122 114 107 102 91 83
23 3/4" 787 572 475 416 376 345 303 273 251 234 220 209 199 179 165
31 1" 1909 1368 1126 981 881 807 703 631 578 537 504 476 452 406 372
37 1-1/4" 2946 2097 1719 1493 1338 1224 1063 953 871 808 757 714 678 608 556
48 1-1/2" 6240 4435 3632 3152 2824 2581 2240 2007 1834 1700 1592 1502 1426 1278 1168
60 2" 13943 9755 7915 6825 6083 5538 4775 4256 3874 3578 3340 3144 2978 2654 2416
Tubing Tubing Length (ft)
EHD Size 200 250 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
13 3/8" 25 22 20 17 15 14 13 12 11 11 10 10 9 9 8
18 1/2" 72 65 59 51 46 42 39 37 34 33 31 30 29 28 27
23 3/4" 145 130 120 105 95 87 81 76 72 69 66 63 61 59 57
31 1" 324 291 267 232 209 191 178 167 157 150 143 137 132 127 123
37 1-1/4" 483 433 396 344 308 282 261 245 231 219 209 201 193 186 180
48 1-1/2" 1014 908 830 720 645 590 547 512 483 459 438 419 403 389 376
60 2" 2083 1857 1690 1457 1299 1183 1092 1020 960 909 865 827 794 764 737
Tables include losses for four 90° bends and two end fittings. Tubing runs with a larger number of bends and/or fittings shall be increased
by an equivalent length of tubing to the following equation: L=1.3n where L is additional length of tubing and n is the number of ad-
ditional fittings and/or bends.