Brochure
Gastite Division, Titeflex Corporation
1116 Vaughn Parkway / Portland, TN 37148
800.662.0208 / www.gastite.com / gastite@gastite.com
75
April 2015
Section 7: Sizing Tables and Pressure Drop Charts
S : S T P D C
FlashShield™ CSST
7.1 CSST Capacity Tables - Natural Gas
Table 7-1
Maximum Capacity of FlashShield™ Flexible Gas Piping in Cubic Feet Per Hour of Natural Gas
with a Gas Pressure of 0.5 PSI or Less and a Pressure Drop of 0.5"WC
(based on a 0.60 specific gravity gas)
Tubing Tubing Length (ft)
EHD Size 5 10 15 20 25 30 40 50 60 70 80 90 100 125 150
13 3/8" 47 32 26 22 20 18 15 14 13 12 11 10 10 8 8
18 1/2" 131 93 76 66 59 54 47 42 38 36 33 32 30 27 24
23 3/4" 251 183 152 133 120 110 97 87 80 75 70 67 63 57 53
31 1" 578 415 341 297 267 244 213 191 175 163 153 144 137 123 113
37 1-1/4" 871 620 508 441 396 362 314 282 258 239 224 211 201 180 164
48 1-1/2" 1834 1304 1068 926 830 759 658 590 539 500 468 442 419 376 343
60 2" 3874 2711 2199 1896 1690 1539 1327 1183 1077 994 928 874 827 737 671
Tubing Tubing Length (ft)
EHD Size 200 250 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
13 3/8" 7 6 5 5 4 4 3 3 3 3 3 3 2 2 2
18 1/2" 21 19 17 15 14 12 11 11 10 10 9 9 8 8 8
23 3/4" 46 42 38 34 30 28 26 24 23 22 21 20 20 19 18
31 1" 98 88 81 70 63 58 54 50 48 45 43 42 40 39 37
37 1-1/4" 143 128 117 102 91 83 77 72 68 65 62 59 57 55 53
48 1-1/2" 298 267 244 212 190 173 161 150 142 135 129 123 118 114 110
60 2" 579 516 470 405 361 329 304 283 267 253 240 230 221 212 205
Table 7-2
Maximum Capacity of FlashShield™ Flexible Gas Piping in Cubic Feet Per Hour of Natural Gas
with a Gas Pressure of 0.5 PSI or Less and a Pressure Drop of 1.0"WC
(based on a 0.60 specific gravity gas)
Tubing Tubing Length (ft)
EHD Size 5 10 15 20 25 30 40 50 60 70 80 90 100 125 150
13 3/8" 67 47 38 32 29 26 22 20 18 17 15 15 14 12 11
18 1/2" 185 131 107 93 83 76 66 59 54 50 47 44 42 38 34
23 3/4" 345 251 209 183 165 152 133 120 110 103 97 92 87 79 72
31 1" 807 578 476 415 372 341 297 267 244 227 213 201 191 172 157
37 1-1/4" 1224 871 714 620 556 508 441 396 362 336 314 297 282 253 231
48 1-1/2" 2581 1834 1502 1304 1168 1068 926 830 759 703 658 621 590 528 483
60 2" 5538 3874 3144 2711 2416 2199 1896 1690 1539 1421 1327 1249 1183 1054 960
Tubing Tubing Length (ft)
EHD Size 200 250 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
13 3/8" 10 8 8 7 6 5 5 5 4 4 4 4 4 3 3
18 1/2" 30 27 24 21 19 17 16 15 14 14 13 12 12 11 11
23 3/4" 63 57 53 46 42 38 36 34 32 30 29 28 27 26 25
31 1" 137 123 113 98 88 81 75 70 67 63 60 58 56 54 52
37 -1/4" 201 180 164 143 128 117 109 102 96 91 87 83 80 77 75
48 1-1/2" 419 376 343 298 267 244 226 212 200 190 181 173 167 161 155
60 2" 827 737 671 579 516 470 434 405 381 361 344 329 315 304 293
Tables include losses for four 90° bends and two end fittings. Tubing runs with a larger number of bends and/or fittings shall be increased
by an equivalent length of tubing to the following equation: L=1.3n where L is additional length of tubing and n is the number of
additional fittings and/or bends.