Section 4: Installation Practices
Regulator Capacity Tables
Table 4-7
Regulator Capacity for Natural Gas with an 8"WC Outlet Pressure
Capacities – 0.64 sp gr gas expressed in CFH (m3/h)
Model Number Outlet Pressure
Operating Inlet Pressure
1/2 PSI (34 mbar) 3/4 PSI (52 mbar) 1 PSI (69 mbar) 1-1/2 PSI (103) mbar 2 PSI (138 mbar)
T325-3-44/Reg8-300 8"WC 145 (4.1) 200 (5.7) 250 (7.1) 250 (7.1) 250 (7.1)
T325-5-44/Reg8-600 8"WC 335 (9.5) 475 (13.5) 550 (15.6) 550 (15.6) 550 (15.6)
T325-7AL-NG01 8"WC 690 (19.5) 970 (27.5) 1250 (35.4) 1250 (35.4) 1250 (35.4)
T325-3L48 (OPD) 8"WC 160 (4.5) 200 (5.6) 200 (5.6) 200 (5.6) 200 (5.6)
T325-5AL600 (OPD) 8"WC 345 (9.6) 425 (11.9) 425 (11.9) 425 (11.9) 425 (11.9)
T325-7L-210D (OPD) 8"WC 650 (18.4) 900 (25.5) 1250 (35.4) 1250 (35.4) 1250 (35.4)
30051-NG 8"WC 386 (10.9) 553 (15.7) 635 (18.0) 850 (24.1) 928 (26.3)
30052-NG 8"WC 386 (10.9) 691 (19.6) 848 (24.0) 1063 (30.1) 1155 (32.7)
30053-NG 8"WC 386 (10.9) 899 (25.5) 1059 (30.0) 1382 (39.1) 1501 (42.5)
30153-NG 8"WC 3189 (90.3) 4638 (131.3) 5297 (150.0) 7230 (204.7) 7891 (223.4)
Capacity value for most typical 2 PSI parallel systems when trunk run is sized to deliver 1 PSI to regulator inlet.
Table 4-8
Regulator Capacity for Natural Gas with an 11"WC Outlet Pressure
Capacities – 0.64 sp gr gas expressed in CFH (m3/h)
Model Number Outlet Pressure
Operating Inlet Pressure
1/2 PSI (34 mbar) 3/4 PSI (52 mbar) 1 PSI (69 mbar) 1-1/2 PSI (103) mbar 2 PSI (138 mbar)
T325-3-44P/Reg11-300 11"WC 93 (2.6) 172 (4.9) 225 (6.4) 250 (7.1) 250 (7.1)
T325-5-44P/Reg11-600 11"WC 211 (6.0) 391 (11.1) 511 (14.5) 550 (15.6) 550 (15.6)
T325-7AL-NG01 11"WC 441 (12.5) 816 (23.1) 1250 (35.4) 1250 (35.4) 1250 (35.4)
T325-3L48* (OPD) 11"WC 120 (3.4) 200 (5.6) 200 (5.6) 200 (5.6) 200 (5.6)
T325-5AL600* (OPD) 11"WC 260 (7.3) 425 (11.9) 425 (11.9) 425 (11.9) 425 (11.9)
T325-7L-210D* (OPD) 11"WC 490 (13.9) 821 (23.2) 1250 (35.4) 1250 (35.4) 1250 (35.4)
30051-NG* 11"WC 297 (8.4) 496 (14.0) 628 (17.8) 778 (22.0) 928 (26.3)
30052-LP 11"WC 297 (8.4) 621 (17.6) 778 (22.0) 967 (27.4) 1155 (32.7)
30053-NG* 11"WC 297 (8.4) 807 (22.9) 1093 (31.0) 1297 (36.7) 1501 (42.5)
30153-NG* 11"WC 2349 (66.5) 4121 (116.7) 5264 (149.1) 6593 (186.7) 7921 (224.3)
Capacity value for most typical 2 PSI parallel systems when trunk run is sized to deliver 1 PSI to regulator inlet.
*Regulator requires in-field adjustment to obtain output pressure of 11".
Table 4-9
Regulator Capacity for Propane with an 11"WC Outlet Pressure
Capacities – 1.52 sp gr gas expressed in kBTUh
Model Number
Outlet Pressure
Operating Inlet Pressure
1/2 PSI (34 mbar) 3/4 PSI (52 mbar) 1 PSI (69 mbar) 1-1/2 PSI (103) mbar 2 PSI (138 mbar)
T325-3-44P/Reg11-300
11"WC
147 270 355 395 395
T325-5-44P/Reg11-600
11"WC
335 620 810 870 870
T325-7AL-NG01
11"WC
700 1290 1811 1811 1811
T325-3L48* (OPD)
11"WC
190 315 315 315 315
T325-5AL600* (OPD)
11"WC
410 670 670 670 670
T 325-7L-210D* (OPD)
11"WC
775 1300 2012 2012 2012
30051-NG*
11"WC
438 798 1028 1385 1584
30052-LP
11"WC
547 997 1285 1731 1981
30053-NG*
11"WC
712 1296 1671 2251 2575
30153-NG*
11"WC
3724 6784 8741 11775 13470
Capacity value for most typical 2 PSI parallel systems when trunk run is sized to deliver 1 PSI to regulator inlet.
*Regulator requires in-field adjustment to obtain output pressure of 11".
Table 4-10
Largest Single Appliance Served by Regulator
Regulator
Natural Gas (CFH) Propane (kBTUh)
0.64 SG gas 1.52 SG gas
T325-3-44P/Reg11-300 147 395
T325-5-44P/Reg11-600 335 870
T325-7AL-NG01 1250 1811
T325-3L48 (OPD) 190 315
T325-5AL600 (OPD) 410 670
T 325-7L-210D (OPD) 1250 2012