System Maintenance Manual

Page 5-16 G1000/GFC700 System Maintenance Manual – C90A/C90GT/C90GTi King Air
Revision F 190-00682-01
GIA2 ARINC 429
Channel LRU Indicator Status
IN 2
(applies only
with SW Image
0636.03 and
subs)
GRS 77 #1
GIA2/GRS 77 #1 data path is functioning correctly.
GIA2/ GRS 77 #1 data path is not functioning correctly.
Load GIA2 configuration file.
Swap GIA1 and GIA2, reconfigure both GIA’s to their new
locations to confirm if the problem is in the original GIA2.
o Replace original GIA2 if box turns to a green
checkmark () after swapping units.
Swap GRS1 and GRS2 (no reconfiguration required) to
confirm if the problem is in the original GRS1.
o Replace original GRS1 if box turns to a green
checkmark () after swapping units.
Check the GIA2/ GRS 77 #1 interconnect wiring for faults.
GIA2/ GRS 77 #1 data path functionality is unknown. Reload
GIA2 configuration files.
IN 5 GDC 74 #2
GIA2/GDC 74 #2 data path is functioning correctly.
GIA2/GDC 74 #2 data path is not functioning correctly.
Load GIA2 and GDC 74 #2 configuration files.
Swap GIA2 and GIA1, reconfigure both GIA’s to their new
locations to confirm if the problem is in the original GIA2.
o Replace original GIA2 if box turns to a green
checkmark () after swapping units.
Check the GIA2/GDC 74 #2 interconnect wiring for faults.
Replace GDC 74 #2 if problem remains.
GIA2/GDC 74 #2 data path functionality is unknown. Reload
GIA2 configuration files.