5.20 Software/Configuration Troubleshooting
Problem Solutions
MFD or PFD displays do not power up:
Ensure that the criteria listed in Section 5.20.1 are
fulfilled for the applicable situation.
Ensure power is present at display backshell
connector.
Troubleshoot per the “Blank Display” GDU section.
Software file load fails:
Ensure that criteria listed in Section 5.20.1 are
fulfilled for the applicable situation.
Ensure that LRU is reporting data on System
Status page (LRU is ‘ONLINE’). Check data path
wiring as needed.
Retry software file load or try using a different card.
Ensure that the MFD is not touched during the
loading process.
Ensure that LRU part number is compatible with
software version and Card Loader. Refer to the
General Arrangement Drawing and to Section 3.8
of this document.
Replace LRU.
Configuration file load fails:
Ensure that the criteria listed in Section 5.20.1 are
fulfilled for the applicable situation.
Ensure that LRU is reporting data on System
Status page (LRU is ‘ONLINE’). Check data path
wiring as needed.
Retry configuration file load or try using a different
card. Ensure that the MFD is not touched during
the loading process.
Ensure that LRU part number is compatible with
Card Loader. Refer to the General Arrangement
Drawing and to Section 3.8 of this document.
Replace LRU.
GIA1 and/or GIA2 to ‘LRU’ data path not
working
Ensure that the criteria listed in Section 5.20.1 are
fulfilled for the applicable situation.
Ensure GIA1 and GIA2 are configured correctly.
Check wiring, connectors & pins as needed.
Software File Mismatch Alert appears in lower
right corner of PFD when started in normal mode:
Ensure that proper software file part number and
version were loaded to LRU. Refer to the General
Arrangement Drawing and to Section 5.20.1.
Check and ensure that correct Card Loader was
used during load process. Refer to the General
Arrangement Drawing.
Reload software to LRU.
After being in configuration mode, the PFD
displays a red AFCS annunciation and cycling of
the transponder field between valid and invalid
states.
With the G1000 system powered on, open the
MFD, PFD 1 (PRI), PFD 1 (SEC), and PFD 2
circuit breakers for approximately 30 seconds,
then close the circuit breakers.