G1000 / GFC 700 System Maintenance Manual - 200/B200 Series King Air Page 5-17
190-00915-01 Revision 8
GIA2 RS-485
Channel LRU Indicator Status
CHNL 1 GEA1
Green
GIA2/GEA1 data path is functioning correctly.
Red
GIA2/GEA1 data path is not functioning correctly.
Verify GEA1 is powered on using the GEA Status page.
Load GIA2 and GEA1 configuration files.
Swap GIA2 and GIA1, reconfigure both GIA’s to their new
locations to confirm if the problem is in the original GIA2.
o Replace original GIA2 if box turns green after
swapping units.
Swap GEA1 and GEA2, reconfigure both GEA’s to their
new locations to confirm if the problem is in the original
GEA1.
o Replace original GEA1 if box turns green after
swapping units.
Check the GIA2/GEA1 interconnect wiring for faults.
Amber
GIA2/GEA1 data path functionality is unknown. Reload GIA2
configuration files.
CHNL 2 GEA2
Green
GIA2/GEA2 data path is functioning correctly.
Red
GIA2/GEA2 data path is not functioning correctly.
Verify GEA2 is powered on using the GEA Status page.
Load GIA2 and GEA2 configuration files.
Swap GIA2 and GIA1, reconfigure both GIA’s to their new
locations to confirm if the problem is in the original GIA2.
o Replace original GIA2 if box turns green after
swapping units.
Swap GEA2 and GEA1, reconfigure both GEA’s to their
new locations to confirm if the problem is in the original
GEA2.
o Replace original GEA2 if box turns green after
swapping units.
Check the GIA2/GEA2 interconnect wiring for faults.
Amber
GIA2GEA2 data path functionality is unknown. Reload GIA2
configuration files.
CHNL 4 GFC 700
Green
GIA2/GFC 700 data path is functioning correctly.
Red
GIA2/GFC 700 data path is not functioning correctly.
Load GIA2 configuration files, GIA Gains file and GSA
software and gains file (if LRU and Card versions are
different).
Reference GFC section for further troubleshooting.
Amber
GIA2/GFC 700 data path functionality is unknown. Reload
GIA2 configuration files.