Installation Instructions

GAT NET.Lock 7020 System
Electrical Connections
44
HB_GAT-NETLOCK7020--EN_12
www.gantner.com
For systems that do not have any GAT NET.Lock 7020 USB locks and are connected in series (see “4.4.2 Sub
Controller Connection”), connect one GAT NET.Power Supply 7020 100-240V / VI to each sub controller. As an
alternative for non-USB systems, the number of power supplies can be reduced as shown in option 2.
To calculate the requirements for an emergency power supply (UPS), allow for a typical power consumption of
3 W (+2 W reserve) per master controller and 90 W per sub controller fully connected with locks.
Option 2: Shared power supply
NOTE! This option is only suitable for systems that do not use any GAT NET.Lock 7020 USB locks.
Connect one GAT NET.Power Supply 7020 100-240V / VI to the master controller and the first and fifth sub
controllers only. A power supply must always be connected to the master controller and the first sub controller.
If 5 or more sub controllers are used in one line, a second power supply is required at the fifth controller.
For the sub controllers that are not directly connected to a power supply, insert one GAT NET.Power Plug
(included with the sub controller) into the power connector.
o The power is then forwarded on to the remaining sub controllers via the RS-485 line.
To calculate the requirements for an emergency power supply (UPS), allow for a typical power consumption of
3 W (+2 W reserve) per master controller and per sub controller fully connected with locks.