Page 6
3E3140 Gallagher T20 Terminal Installaon Note | Edion 16 | March 2016
Copyright © Gallagher Group Limited
HBUS
Device
"T" or "Star" circuits are
not permied between
HBUS devices
Controller 6000
H1
H4
H8
H5
HBUS
Device
Terminate
HBUS
Device
Terminate
HBUS Module
HBUS
Device
HBUS
Device
Terminate
HBUS
Device
Terminate
HBUS
Device
Cable distance
Cable type Cable format* Single terminal
connected using
HBUS data only
in a single cable
Single terminal
connected using
Cardax IV data only
in a single cable***
Single terminal
connected using
power and data
in a single cable
CAT 5e or
beer**
4 twisted pair
Each 2 x 0.2 mm
2
(24 AWG)
500 m (1640 ) 200 m (650 ) 50 m (165 )
BELDEN
9842**
(shielded)
2 twisted pair
Each 2 x 0.2 mm
2
(24 AWG)
500 m (1640 ) 200 m (650 ) 50 m (165 )
SEC472 4 x 0.2 mm
2
Not twisted pairs
(24 AWG)
400 m (1310 ) 200 m (650 ) 50 m (165 )
SEC4142 4 x 0.4 mm
2
Not twisted pairs
(21 AWG)
400 m (1310 ) 200 m (650 ) 100 m (330 )
* The matching of wire sizes to equivalent wire gauges are only approximate.
** Recommended cable types for opmal HBUS RS485 performance.
*** Not applicable for PIV or Alarm Terminal installaons.
Notes:
• Shielded cable may reduce the obtainable cable length. Shielded cable should be
grounded at the Controller end only.
• If other cable types are used, operang distances and performance may be reduced
depending on the cable quality.
• The recommendaon for opmal performance is up to 20 T20 terminals can be connected
to one Controller 6000. Of these 20 terminals, up to 4 could be congured for alarm zone
(or fence controller) management.
A terminal is congured for alarm zone management when it has either Alarm Zones
congured on the Alarm Zones properes page or items congured upon its mimic panel.