3E3140 Gallagher T20 Terminal Installaon Note | Edion 16 | March 2016
Copyright © Gallagher Group Limited
12 Technicalspecicaons
Roune maintenance: Not applicable for this terminal.
Cleaning: This terminal should be cleaned with mild soapy
water only. Do not use solvents or abrasives.
Voltage: 9 Vdc - 16 Vdc
Current: Inacve
1
Acve
2
T20 Mifare Terminal (at 9 Vdc): 191 mA 300 mA
T20 Mifare Terminal (at 13.6 Vdc): 140 mA 200 mA
T20 Mul Tech Terminal (at 9 Vdc): 262 mA 335 mA
T20 Mul Tech Terminal (at 13.6 Vdc): 189 mA 282 mA
T20 Alarms Terminal (at 9 Vdc): 140 mA 250 mA
T20 Alarms Terminal (at 13.6 Vdc): 110 mA 190 mA
Temperature range: -30 °C to +70 °C (-22 °F to +158 °F)
Note: Direct sunlight may increase the internal
terminal temperature above the ambient
temperature level.
Humidity: 95% non condensing
4
Environmental protecon: IP66 (independently veried)
Impact rang: IK08 (independently veried)
Unit dimensions: Height 179.5 mm (7.1 in)
Width 95.7 mm (3.8 in)
Depth 23 mm (0.9 in)
Maximum number of readers on one HBUS cable: 20
Maximum number of alarms management
terminals
3
on one Controller 6000:
4
Maximum number of terminals on one Controller
6000:
20
1
The terminal is idle. The screen is on.
2
A card is being read or the screen is at maximum brightness.
3
A terminal is congured for alarm zone management/fence controller management when it has either
Alarm Zones congured on the Alarm Zones properes page or items congured upon its mimic panel.
4
Gallagher T Series readers are UL humidity tested and cered to 85% and have been independently
veried to 95%.
Note: The current values stated above have been reported using the default conguraon of an
HBUS terminal (HBUS Terminal or HBUS Alarms Only Terminal) in Command Centre. Changing the
conguraon may vary the current value.