User's Manual
Mount the backplate using countersunk headed screws adjacent to the opening
edge of the door and at a convenient height (recommended height is 5' (1.5m)
to top of unit).
If fixing hole ’A’ is used then the breakout must be removed and the screw must
not protrude.
Feed the cable from the controller through the backplate.
If the wall tamper function is to be used then the small hole in breakout ‘B’ may
be used to mark the position of the wall screw before the breakout is removed.
An appropriate wall screw should then be adjusted in height to protrude through
the hole to activate the tamper lever.
2
1
Mount the Backplate
Reader Connections
The S874 is a
reader can be set to use Wiegand or
The S874 reader will read smartMAX encoded MIFARE cards and card serial
numbers from most ISO 14443A smart cards which have a 4-byte UID (User
Identification). The reader may be configured to read other card types by
presenting a programming card to the reader during start up.
For additional information regarding the installation, configuration and proper
use of this product:
SMS User Guide, P/N 9600-0429, M2150 Access Control Design Guide, P/N
9600-0420, M2150 Intrusion Guide, P/N 9600-0540 and M2150 UL1076
Compliance Manual, P/N 9600-0449.
contactless smart-card reader, with LED’s and keypad. The
20mA current loop communications.
The securing screw ‘C’ is integral to the backplate and is unscrewed via the small hole in the enclosure so that the
screw head locates in the counterbored holes on the inside of the enclosure.
You should find
that the backplate
has holes for
connection to
most standard
electrical
backboxes.
C
A
B
Installation and User Instructions for S874 Keypad Readers
0V
RX+
RX-
TX+
TX-
12V
Controller
0V
TX+
TX-
RX+
RX-
+V
Reader
TB1
20mA current loop
0V
Green
Data 0
Red
Data 1
12V
Controller
0V
GRN
0
+V
Use Belden
9537 Cable
Wiegand
RED
1
Reader
TB1
Connect shield at
controller end only.
Connect shield at
controller end only.
Twisted pairs (use
Belden 9503 Cables)
Note: Use SW1 switch2 to select the communications mode (See Step 3).
Note:
1). Consult local AHJ (Authority Having Jurisdiction) when installing access control readers and locking mechanisms to
any portal in an egress path.
2). The use of Fail Closed / secure configuration shall be determined by local building codes and the local AHJ.
3). Wiring methods shall be in accordance with NEC (National Electrical Code) ANSI/NFPA 70.
4). The Wiegand connections are not allowed under UL1076 unless a separate tamper switch is provided.
Slide the ferrite sleeve onto cable before wiring terminal block. Ferrite to be placed 50mm (2") up cable and held in place with
cable ties.
Note: The FERRITE must be fitted!