Users Manual
Operating Manual Smart Weather Sensor
164 G. Lufft Mess- und Regeltechnik GmbH, Fellbach, Germany
19.9.2.1 Command Averaging Interval Temperature Measurement
Command Code: TMI
Request: TMI
Adjust: TMI=<value>
Value Range: 1 … 10
19.9.2.2 Command Evaporation Parameter
Command Code: EVP
Request: EVP
Adjust: EVP=<value>
Value Range: 0.0 … 0.24 …100.0
19.9.2.3 Command Rain Correction Factor
Command Code: RCF
Request: RCF
Adjust: RCF=<value>
Value Range: 0.2 … 1.0 …5.0
19.9.2.4 Command Snow Correction Factor
Command Code: SCF
Request: SCF
Adjust: SCF=<value>
Value Range: 0.2 … 1.0 …5.0
19.9.2.5 Command Precipitation Type Follow Up Time
Command Code: PTT
Request: PTT
Adjust: PTT=<value>
Value Range: 0 … 120 …3600 [sec]
19.9.2.6 Command Heating Operation Mode
Command Code: HTM
Request: HTM
Adjust: HTM=<value>
Value Range: 0 …3
<value>
Operation Mode
0
Automatic
1
Mode 1
2
Off
3
Eco Mode 1
See Chapter 10.5 for heating operation modes