Users Manual

Operating Manual Smart Weather Sensor
160 G. Lufft Mess- und Regeltechnik GmbH, Fellbach, Germany
19.9 (WS100-UMB only) Communication: UMB-ASCII 2.0 Protokoll
UMB-ASCII 2.0 provides query of measurement values and sensor configuration in a human
readable format. Details and general commands can be found in the UMB-ASCII 2.0 manual
(Manual_Lufft_UMB-ASCII_2_0_Version_1_1_en.pdf).
The separators used for the output strings can be adjusted to the requirements of a logger
(see Chapter 0)
In addition to the general configuration commands described in the UMB-ASCII 2.0 manual
device specific commands for configuration work have been defined for the WS100-UMB
(see Chapter 19.9.2)
In UMB-ASCII 2.0 mode defined sets of measurement values can be transmitted
automatically at adjustable intervals without further query commands. WS100-UMB provides
four standard sets:
- S1: General precipitation values, metric units
- S5: General precipitation values, imperial units
- S10: Service channels (drop distribution, air temperature), metric units
- S15: Service channels (drop distribution, air temperature), imperial units
19.9.1 Format of the Standard Sets
The following list uses UMB-ASCII 2.0 factory setting separators.
Byte
Wert
Beschreibung
0
<STX>
02 Hex
1-4
<Add>
Device address hex, e.g. 7001 for WSx-UMB with device ID 1
5
:
3A hex
6-7
<Nr>
Request number hex, always 00 for auto transmission
8
:
3A hex
9-10
SS
<Cmd>, standard set
11
;
3B hex
12-
<Set>
standard set number
=
3D hex
<TelNo>
Number of auto transmitted messages from start
;
3B hex
<SerNo>
Lufft serial number
;
3B vex
measurement value 1
;
3B hex
measurement value 2
;
3B hex
….
….
;
3B hex
measurement value n
;
3B hex
<Status>
device status, hex
:
3A hex
<Status>
command status, hex
:
3A hex
<CheckSum>
check sum, hex
<CR>
0D hex
<LF>
0A hex
<EOT>
04 hex
Depending on the measurement value type the output is formatted as integer or fixed point
representation. Measurement value lists of the standard sets follow: