25.8 Change of Priority for Unacknowledged Warning
IMO MSC302(87) requires that a Warning be changed to an Alarm if it is not acknowl-
edged within 60 seconds. The change of priority feature is enabled or disabled during
the installation.
25.9 How to Temporarily Silence the Buzzer
The FMD-3xx0 series and the FCR-2xx9 series are compliant with IEC 61924-2, which
has a provision to allow the temporary silencing of the buzzer for 30 seconds against
any alert, from the equipment that generated the alert or from the AMS. The buzzer
again sounds after 30 seconds if the alert is not acknowledged.
How category A alerts are treated at the AMS
The buzzer given against a category A alert can be temporarily silenced at the AMS,
by clicking the alert on any AMS mode window (see section 25.13.2) or pushing the
ALARM ACK key on a Control Unit. However, the alert must be acknowledged from
the equipment that generated the alert. The AMS indicates acknowledgement after
the alert is acknowledged at the equipment.
25.10 Buzzer Patterns
The AMS has two buzzer patterns, legacy and IEC 61924-2, and one is chosen at in-
stallation.
Legacy buzzer pattern
This buzzer sounds continuously until an emergency/alarm or warning is acknowl-
edged.
60
seconds
Not acknowledged
A Warning
is generated.
The Warning becomes an Alarm and
is then transferred to the BNWAS.
Acknowledge
Acknowledge
The buzzer sounds continuously.
Emergency/Alarm or
Warning generated