Install Instructions

February, 2000
Supersedes Issue of
July, 1985
75-HEF14
Contact Kit, Innova Controllers
00, 0, 1, 1P, & 1
3
/
4
Class 14, 22, 30, 40, & 43
Cat No 75AF14 thru 75EF14
Instructions
KIT DATA
Use with sizes 00 through 1
3
/4 Innova series controllers. Each
kit catalog number applies to specic controller sizes as follows:
Catalog Contact Kit Innova Series
Number for Size
75AF14 Interlock Pole 00, 0, 1, 1P, 1
3
/4
75BF14 Power Pole 00
75CF14 Power Pole 0
75DF14 Power Pole 1
75EF14 Power Pole 1P, 1
3
/4
Rating: The contact assumes the rating of the control on which
the contact is mounted.
Contents of kits: Each kit contains the following:
1 A line side stationary contact
1 B load side stationary contact
2 C self-tapping screws
1 D spring
1 E spring retainer for kits 75AF14, 75BF14, and 75CF14 only
1 F movable bar
CONTACT REPLACEMENT
When one power pole requires contact replacement, replacing
the contacts on all power poles of the controller is recommend-
ed to assure proper contact mating.
Disassembly
1. Remove the contact board cover from the controller.
2. For a controller equipped with an overload relay, the overload
relay must be removed when replacing power pole contacts.
For interlock pole contact replacement, removing the over-
load relay is not required.
a. Tag and remove wires from the overload relay load ter-
minals.
b. The overload relay mounting plate is secured to the
enclosure or mounting panel with one or two screws;
remove screw(s).
c. Loosen the three screws at the contactor load terminals.
A slot in the overload relay mounting plate engages a tab
on the contactor mounting plate. Tilt the overload relay
slightly to disengage the slot from the tab and pull the
overload relay from the contactor.
3. Tag and remove wires at the contactor line and load termi-
nals for the pole being repaired. Do not remove wires from
a lug. Remove the terminals clamps, line lug or load side
power take o lug, as applicable. Retain the terminal parts
and screws.
Hazardous voltage.
Can cause death, serious personal
injury, or property damage.
Disconnect power before working on
this equipment.
(For Engineering Reference Only - Rev. D)