Brochure

Table Of Contents
Circuit Breaker/MSP 3RV1
SIRIUS System Manual
2-70 GWA 4NEB 430 0999-02 DS 01
No backup fuse required because it is short circuit-proof up to 100 kA.
Short circuit-proof up to min. 50 kA.
1 A backup fuse is only required if the short-circuit current at the installation location is > I
cu
.
2 10% overvoltage
3 5% overvoltage
Circuit
breaker
Rated
current
I
n
To 240 VAC
2
)To 400 VAC
2
)/415 V
3
) To 440 VAC
2
)/460 V
3
) To 500 VAC
2
)/525 V
3
) To 690 VAC
2
)
I
cu
I
cs
Max. I
cu
I
cs
Max. I
cu
I
cs
Max. I
cu
I
cs
Max. I
cu
I
cs
Max.
Fuse Fuse Fuse Fuse Fuse
(gL/gG) (gL/gG) (gL/gG) (gL/gG) (gL/gG)
Type A kAkAA kA kA A kAkA A kA kA A kAkAA
3RV1. 41
Frame size S3
40
100 100 50 25 125
1
) 50 20 125
1
)12 6100 6 363
50
100 100 50 25 125
1
) 50 20 125
1
)12 6100 6 380
63
100 100 50 25 160
1
) 50 20 160
1
)12 6100 6 380
75
100 100 50 25 160
1
) 50 20 160
1
)8 4125 5 3100
90
100 100 50 25 160
1
) 50 20 160
1
)8 4125 5 3125
100
100 100 50 25 160
1
) 50 20 160
1
)8 4125 5 3125
3RV1.42
Frame size S3
With increased
switching
capacity
16
100 100 100 50 100 50 •30158012763
20
100 100 100 50 100 50 •30158012763
25
100 100 100 50 100 50 •30158012763
32
100 100 100 50 100 50 •221110012763
40
100 100 100 50 100 50 •18916012680
50
100 100 100 50 100 50 •157.5160105100
63
100 100 100 50 70 50 200
1
) 15 7.5 160 7.5 4 100
75
100 100 100 50 70 50 200
1
)10 5160 6 3125
90
100 100 100 50 70 50 200
1
)10 5160 6 3160
100 100 100 100 50 70 50 200
1
)10 5160 6 3160