Brochure
Table Of Contents
- 2 3RV1 Circuit Breaker/MSP 1)
- 2.1 Specifications/regulations/approvals
- 2.2 Device description
- 2.3 Application and areas of use
- 2.4 Accessories
- 2.4.1 Attachable accessories: Overview
- 2.4.2 Auxiliary contacts 3RV19 01-.., alarm switch 3RV19 21-111 and auxiliary release 3RV19 .2-....
- 2.4.3 Motorized remote-control mechanism 3RV19 .6-....
- 2.4.4 Disconnecting/isolator module 3RV19 .8-1A
- 2.4.5 Thru-the door rotary operators 3RV19 .6-..
- 2.4.6 Terminals for "Combination Motor Controller Type E" in acc. with UL 508
- 2.4.7 Enclosures and mounting accessories
- 2.4.8 Busbar adapter 8US1 (Fastbus system)
- 2.4.9 Isolated 3-phase busbar system
- 2.4.10 Link module for connection to a contactor
- 2.5 Mounting and connection
- 2.6 Dimensional drawings (measurements in mm)
- 2.7 Technical specifications
- 2.7.1 General specifications
- 2.7.2 Permissible rating of approved devices for North America, u s
- 2.7.3 Short-circuit breaking capacity Icn in acc. with IEC 60 947-2
- 2.7.4 Limiter function with standard devices for 500 VAC and 690 VAC in acc. with IEC 60 947-2
- 2.7.5 Characteristics
- 2.7.6 Installation guidelines
- 2.8 Application notes for the use of 3RV1 downstream from frequency converters/ inverter with pulsing voltage
3RV1 Circuit Breaker/MSP
SIRIUS System Manual
GWA 4NEB 430 0999-02 DS 01
2-7
Other accessories Other accessories for circuit breaker/MSPs:
•Alarm switch
• Disconnecting module
• Isolated 3-phase busbar system
• Busbar adapter
• Rotary switches
• Terminals for "Combination Motor Controller Type E" in acc. with UL 508
• Housing and front plates
2.2.2 Operation
Current setting Using a screwdriver, set the load rated current (current setting) I
e
on the
scale of the 3RV1.
The proper dial setting will depend how the 3RV1 will be installed. There are
two determining factors:
1. Stand-alone installation: without a directly mounted contactor and clear-
ance left and right of a minimum 10 mm.
2. Side-by-side installation: with a directly mounted contactor and clear-
ance left and right of less than 10 mm. This is the typical installation
method.
Note the two possible dial markings on the dial:
• Dash mark: Is the dial marking used when the 3RV1 is being applied in
stand-alone installation
• Triangle mark: Is the dial marking used when the 3RV1 is being applied in
side-by-side installation
In both cases the ambient temperature may be +60 °C and the complete
current range can be used up to the highest setting. The relevant dial mark-
ing (Dash or Triangle) should be set according to the required current set-
ting. At temperatures over +60 °C current derating is necessary. The maxi-
mum allowable current setting for an ambient temperature of +70 °C can be
determined by a slightly longer setting line on the current scale.
Fig. 2-2: Current adjustment I
e
adjustment (example: frame size S00)
360° o.k.
RV-00222
I
e
max. + 60 °C
max. + 70 °C
A