Circuit Breaker/MSP 3RV1
SIRIUS System Manual
2-68 GWA 4NEB 430 0999-02 DS 01
3RV10.A as "Combination Motor Controller Type E"
Since July 16th 2001, 1 inch air clearance and 2 inch creepage distance is required for a "Combination Motor Controller Type E" on the
input side with UL 508 The 3RV10 in frame sizes S0 and S3 are therefore approved with the terminal blocks listed below in acc. with
UL 508.
The 3RV10 in frame size S2 already complies with the required air clearance and creepage distance as a basic unit. These extended air
clearances and creepage distances are not required for CSA. The terminal blocks are therefore not required for use as a "Combination
Motor Controller Type E" in acc. with CSA. 3RV10’s are certified as "Combination Motor Controller Ty p e E " under the following file num-
bers with the listed data:
u File No. E156943, Product Class NKJH
s Master Contract 165071, Product Class 3211 08
Hp rating = output power in horse power (maximum motor power)
FLA = full load amps
1) 1) Corresponds to "short circuit breaking capacity" in acc. with UL
2) Not required by CSA
Motor Starter Protector Hp rating Rated current To 240 VAC To AC 480 Y/277 V To AC 600 Y/347 V
For FLA max. I
n
I
cu
1
) I
cu
1
) I
cu
1
)
Type V 1-phase 3-phase A kA kA kA
0.11 to 1.6 50 50 30
3RV10 21 2505030
+ 3RV19 28-1H
2)
115 2 2.5 50 50 30
200 3 3.2 50 50 30
Frame size S0
230 3 4 50 50 30
460 15 5 50 50 30
FLA max. 22 A, 480 V
575/600 10 6.3 50 50 30
12.5 A, 600 V
8505030
10 50 50 30
12.5 50 50 30
16 50 50
20 50 50
22 50 50
11 to 16 50 50 25
3RV10 31
20 50 50 25
115 3 —25 50 50 25
Frame size S2
200 15 32 50 50 25
230 10 20 40 50 50 25
FLA max. 50 A, 600 V
460 40 45 50 50 25
575/600 50 50 50 50 25
3RV10 41 11 to 16 50 50 30
+ 3RV1946-4GA07
2)
20 50 50 30
115 10 —25 50 50 30
Frame size S3
200 20 30 32 50 50 30
230 20 40 40 50 50 30
FLA max. 100 A, 480V
460 75 50 50 50 30
75 A, 600 V
575/600 75 63 50 50 30
75 50 50 30
90 50 50
100 50 50
Rating of the control switches and alarm switches
Side-mount
auxiliary contact with
1NO + 1NC, 2NO,
2NC, 2NO + 2NC
and alarm switch
Transverse
auxiliary contact with
1 changeover contact
Transverse
auxiliary contact with
1 NO + 1 NC, 2 NO
Max. rated voltage
In acc. with NEMA
u VAC 600 240
In acc. with NEMA
s VAC 600 240
Continuous current A 10 5 2.5
Switching capacity A600 B600 C300
Q300 R300 R300