Brochure
Table Of Contents
- 2 3RV1 Circuit Breaker/MSP 1)
- 2.1 Specifications/regulations/approvals
- 2.2 Device description
- 2.3 Application and areas of use
- 2.4 Accessories
- 2.4.1 Attachable accessories: Overview
- 2.4.2 Auxiliary contacts 3RV19 01-.., alarm switch 3RV19 21-111 and auxiliary release 3RV19 .2-....
- 2.4.3 Motorized remote-control mechanism 3RV19 .6-....
- 2.4.4 Disconnecting/isolator module 3RV19 .8-1A
- 2.4.5 Thru-the door rotary operators 3RV19 .6-..
- 2.4.6 Terminals for "Combination Motor Controller Type E" in acc. with UL 508
- 2.4.7 Enclosures and mounting accessories
- 2.4.8 Busbar adapter 8US1 (Fastbus system)
- 2.4.9 Isolated 3-phase busbar system
- 2.4.10 Link module for connection to a contactor
- 2.5 Mounting and connection
- 2.6 Dimensional drawings (measurements in mm)
- 2.7 Technical specifications
- 2.7.1 General specifications
- 2.7.2 Permissible rating of approved devices for North America, u s
- 2.7.3 Short-circuit breaking capacity Icn in acc. with IEC 60 947-2
- 2.7.4 Limiter function with standard devices for 500 VAC and 690 VAC in acc. with IEC 60 947-2
- 2.7.5 Characteristics
- 2.7.6 Installation guidelines
- 2.8 Application notes for the use of 3RV1 downstream from frequency converters/ inverter with pulsing voltage
Circuit Breaker/MSP 3RV1
SIRIUS System Manual
2-68 GWA 4NEB 430 0999-02 DS 01
3RV10.A as "Combination Motor Controller Type E"
Since July 16th 2001, 1 inch air clearance and 2 inch creepage distance is required for a "Combination Motor Controller Type E" on the
input side with UL 508 The 3RV10 in frame sizes S0 and S3 are therefore approved with the terminal blocks listed below in acc. with
UL 508.
The 3RV10 in frame size S2 already complies with the required air clearance and creepage distance as a basic unit. These extended air
clearances and creepage distances are not required for CSA. The terminal blocks are therefore not required for use as a "Combination
Motor Controller Type E" in acc. with CSA. 3RV10’s are certified as "Combination Motor Controller Ty p e E " under the following file num-
bers with the listed data:
u File No. E156943, Product Class NKJH
s Master Contract 165071, Product Class 3211 08
Hp rating = output power in horse power (maximum motor power)
FLA = full load amps
1) 1) Corresponds to "short circuit breaking capacity" in acc. with UL
2) Not required by CSA
Motor Starter Protector Hp rating Rated current To 240 VAC To AC 480 Y/277 V To AC 600 Y/347 V
For FLA max. I
n
I
cu
1
) I
cu
1
) I
cu
1
)
Type V 1-phase 3-phase A kA kA kA
0.11 to 1.6 50 50 30
3RV10 21 2505030
+ 3RV19 28-1H
2)
115 2 — 2.5 50 50 30
200 3 7½ 3.2 50 50 30
Frame size S0
230 3 7½ 4 50 50 30
460 — 15 5 50 50 30
FLA max. 22 A, 480 V
575/600 — 10 6.3 50 50 30
12.5 A, 600 V
8505030
10 50 50 30
12.5 50 50 30
16 50 50 —
20 50 50 —
22 50 50 —
11 to 16 50 50 25
3RV10 31
20 50 50 25
115 3 —25 50 50 25
Frame size S2
200 7½ 15 32 50 50 25
230 10 20 40 50 50 25
FLA max. 50 A, 600 V
460 — 40 45 50 50 25
575/600 — 50 50 50 50 25
3RV10 41 11 to 16 50 50 30
+ 3RV1946-4GA07
2)
20 50 50 30
115 10 —25 50 50 30
Frame size S3
200 20 30 32 50 50 30
230 20 40 40 50 50 30
FLA max. 100 A, 480V
460 — 75 50 50 50 30
75 A, 600 V
575/600 — 75 63 50 50 30
75 50 50 30
90 50 50 —
100 50 50 —
Rating of the control switches and alarm switches
Side-mount
auxiliary contact with
1NO + 1NC, 2NO,
2NC, 2NO + 2NC
and alarm switch
Transverse
auxiliary contact with
1 changeover contact
Transverse
auxiliary contact with
1 NO + 1 NC, 2 NO
Max. rated voltage
• In acc. with NEMA
u VAC 600 240
• In acc. with NEMA
s VAC 600 240
Continuous current A 10 5 2.5
Switching capacity A600 B600 C300
Q300 R300 R300