Brochure
Table Of Contents
- 2 3RV1 Circuit Breaker/MSP 1)
- 2.1 Specifications/regulations/approvals
- 2.2 Device description
- 2.3 Application and areas of use
- 2.4 Accessories
- 2.4.1 Attachable accessories: Overview
- 2.4.2 Auxiliary contacts 3RV19 01-.., alarm switch 3RV19 21-111 and auxiliary release 3RV19 .2-....
- 2.4.3 Motorized remote-control mechanism 3RV19 .6-....
- 2.4.4 Disconnecting/isolator module 3RV19 .8-1A
- 2.4.5 Thru-the door rotary operators 3RV19 .6-..
- 2.4.6 Terminals for "Combination Motor Controller Type E" in acc. with UL 508
- 2.4.7 Enclosures and mounting accessories
- 2.4.8 Busbar adapter 8US1 (Fastbus system)
- 2.4.9 Isolated 3-phase busbar system
- 2.4.10 Link module for connection to a contactor
- 2.5 Mounting and connection
- 2.6 Dimensional drawings (measurements in mm)
- 2.7 Technical specifications
- 2.7.1 General specifications
- 2.7.2 Permissible rating of approved devices for North America, u s
- 2.7.3 Short-circuit breaking capacity Icn in acc. with IEC 60 947-2
- 2.7.4 Limiter function with standard devices for 500 VAC and 690 VAC in acc. with IEC 60 947-2
- 2.7.5 Characteristics
- 2.7.6 Installation guidelines
- 2.8 Application notes for the use of 3RV1 downstream from frequency converters/ inverter with pulsing voltage
Circuit Breaker/MSP 3RV1
SIRIUS System Manual
GWA 4NEB 430 0999-02 DS 01
2-67
2.7.2 Permissible rating of approved devices for North America, u s
In North America the 3RV1 is not approved as a “circuit breaker” and is commonly known as a Motor Starter Protector (MSP). The
SIRIUS 3RV1 series are approved for
u/s and can also be used in acc. with UL 508 and C22.2 No.14 with a contactor as a Type F combi-
nation starter. You can use these MSPs as a "Manual Motor Starter" for "Group Fusing" or for "Group Installation" or as a "Combination Motor
Controller Ty p e E ".
3RV1 as a "Manual Motor Starter"
When the 3RV1 is used as a "Manual Motor Starter", it is always with a device for short-circuit protection (upstream short-circuit pro-
tection device). Any fusible link (“group fusing”) or UL 489 listed circuit breaker (“group installation”) can be used as a device for short-
circuit protection. The type and size are selected in acc. with the American NFPA 70 standard, Article 430-53 (c) for adequate protec-
tion of supply wiring.
Accreditation was issued under the following file numbers with the listed data:
u File No. E47705, Product Class NLRV
s Master Contract 165071, Product Class 3211 05
Motor Starter Protector Hp rating Rated current To 240 VAC To AC 480 Y/277 V To AC 600 Y/347 V
For FLA max. I
n
I
cu
1
) I
cu
1
) I
cu
1
)
Type V 1-phase 3-phase A kA kA kA
0.11 to 2 65 65 10
3RV10 11 2.5 65 65 10
3RV16 11-0BD10
115 ½ - 3.2 65 65 10
200 1½ 3 4 65 65 10
Frame size S00
230 2 3 5 65 65 10
460 - 7½ 6.3 65 65 10
FLA max. 12 A, 600 V
575/600 - 10 8 65 65 10
10 65 65 10
12 65 65 10
0.11 to 3.2 65 65 30
3RV10 21/3RV11 21 4656530
3RV13 21 5656530
115 2 - 6.3 65 65 30
Frame size S0 200 3 7½ 8 65 65 30
230 5 7½ 10 65 65 30
FLA max. 25 A, 600 V 460 - 15 12.5 65 65 30
575/600 - 20 16 65 65 30
20 65 65 30
22 65 65 30
25 65 65 30
3RV10 31/3RV11 31 11 to 16 65 50 25
3RV13 31 20 65 65 25
115 3 - 25 65 65 2 5
Frame size S2 200 7½ 15 32 65 65 25
230 10 20 40 65 65 25
FLA max. 50 A, 600 V 460 - 40 45 65 65 25
575/600 - 50 50 65 50 25
11 to 16 65 65 30
3RV10 41/3RV10 42 20 65 65 30
3RV11 42 115 10 - 25 65 65 30
3RV13 41/3RV13 42 200 20 30 32 65 65 30
230 20 40 40 65 65 30
Frame size S3 460 - 75 50 65 65 30
575/600 - 100 63 65 65 30
FLA max. 99 A, 600 V 75 65 65 30
90 65 65 30
100 (99) 65 65 30
Hp rating = output power in horse power (maximum motor power)
FLA = full load amps
1) 1) Corresponds to "short circuit breaking capacity" in acc. with UL