- 2 3RV1 Circuit Breaker/MSP 1)
- 2.1 Specifications/regulations/approvals
- 2.2 Device description
- 2.3 Application and areas of use
- 2.4 Accessories
- 2.4.1 Attachable accessories: Overview
- 2.4.2 Auxiliary contacts 3RV19 01-.., alarm switch 3RV19 21-111 and auxiliary release 3RV19 .2-....
- 2.4.3 Motorized remote-control mechanism 3RV19 .6-....
- 2.4.4 Disconnecting/isolator module 3RV19 .8-1A
- 2.4.5 Thru-the door rotary operators 3RV19 .6-..
- 2.4.6 Terminals for "Combination Motor Controller Type E" in acc. with UL 508
- 2.4.7 Enclosures and mounting accessories
- 2.4.8 Busbar adapter 8US1 (Fastbus system)
- 2.4.9 Isolated 3-phase busbar system
- 2.4.10 Link module for connection to a contactor
- 2.5 Mounting and connection
- 2.6 Dimensional drawings (measurements in mm)
- 2.7 Technical specifications
- 2.7.1 General specifications
- 2.7.2 Permissible rating of approved devices for North America, u s
- 2.7.3 Short-circuit breaking capacity Icn in acc. with IEC 60 947-2
- 2.7.4 Limiter function with standard devices for 500 VAC and 690 VAC in acc. with IEC 60 947-2
- 2.7.5 Characteristics
- 2.7.6 Installation guidelines
- 2.8 Application notes for the use of 3RV1 downstream from frequency converters/ inverter with pulsing voltage
Circuit Breaker/MSP 3RV1
SIRIUS System Manual
GWA 4NEB 430 0999-02 DS 01
2-65
Ty p e 3RV1. 1 3RV1. 2 3RV1. 3 3RV1. 4
Shock resistance In acc. with IEC 68 Part 2-27 g/ms 25/11 (rectangular and sine pulse)
Degree of protection In acc. with IEC 60 529 IP20 IP20
3
)
Shock protection In acc. with DIN VDE 0106 Part
100
protected against touching by fingers
Temperature compensation In acc. with IEC 60 947-4-1 °C -20 to +60
Phase loss sensitivity In acc. with IEC 60 947-4-1 Yes
Explosion protection In acc. with DIN VDE 0165 and EN 50 019 Yes for 3RV10 (Class 10), 3RV11(Class 10)
Isolating function In acc. with IEC 60 947-2 Yes
Main and emergency-stop switch features
4
) In acc. with IEC 60 204-1
(VDE 0113)
Ye s
Safe isolation between the main circuit and the
auxiliary circuit required for PELV applications
In acc. with DIN VDE 0106 Part 101
• to 400 V + 10 % Ye s
• to 415 V+ 5 % (higher voltage on request) Yes
Mechanical life Operating
cycles
100,000 50,000
Electrical life 100,000 25,000
Max. switching frequency per hour (motor star-
tups)
1/h 15
1) Reduction in current above +60 °C 3) Connection room IP00
2) With molded-plastic housing 500 V 4) With corresponding accessories