Brochure
Table Of Contents
- 2 3RV1 Circuit Breaker/MSP 1)
- 2.1 Specifications/regulations/approvals
- 2.2 Device description
- 2.3 Application and areas of use
- 2.4 Accessories
- 2.4.1 Attachable accessories: Overview
- 2.4.2 Auxiliary contacts 3RV19 01-.., alarm switch 3RV19 21-111 and auxiliary release 3RV19 .2-....
- 2.4.3 Motorized remote-control mechanism 3RV19 .6-....
- 2.4.4 Disconnecting/isolator module 3RV19 .8-1A
- 2.4.5 Thru-the door rotary operators 3RV19 .6-..
- 2.4.6 Terminals for "Combination Motor Controller Type E" in acc. with UL 508
- 2.4.7 Enclosures and mounting accessories
- 2.4.8 Busbar adapter 8US1 (Fastbus system)
- 2.4.9 Isolated 3-phase busbar system
- 2.4.10 Link module for connection to a contactor
- 2.5 Mounting and connection
- 2.6 Dimensional drawings (measurements in mm)
- 2.7 Technical specifications
- 2.7.1 General specifications
- 2.7.2 Permissible rating of approved devices for North America, u s
- 2.7.3 Short-circuit breaking capacity Icn in acc. with IEC 60 947-2
- 2.7.4 Limiter function with standard devices for 500 VAC and 690 VAC in acc. with IEC 60 947-2
- 2.7.5 Characteristics
- 2.7.6 Installation guidelines
- 2.8 Application notes for the use of 3RV1 downstream from frequency converters/ inverter with pulsing voltage
Circuit Breaker/MSP 3RV1
SIRIUS System Manual
2-64 GWA 4NEB 430 0999-02 DS 01
2.7 Technical specifications
2.7.1 General specifications
Ty p e 3RV1. 1 3RV1. 2 3RV1. 3 3RV1. 4
Specifications
• IEC 60 947-1, EN 60 947-1 (VDE 0660 Part 100) Yes
• IEC 60 947-2, EN 60 947-2 (VDE 0660 Part 101) Yes
• IEC 60 947-4-1, EN 60 947-4-1 (VDE 0660 Part 102) Yes
Frame size S00 S0 S2 S3
Pole number 3
Max. rated current I
nmax
(= max. rated operational current I
e
) A12 25 50 100
Permissible ambient temperature
Storage/transportation °C -50 to +80
Operation °C -20 to +70
1
)
Permissible rated current with the following internal cubicle temperature:
•+60 °C %100
•+70 °C %87
Circuit breaker in housing
Permissible rated current with the following ambient housing temperature:
•+35 °C %100
•+60 °C %87
Rated operational voltage U
e
V 690
2
)
Rated frequency Hz 50/60
Rated insulation voltage U
i
V 690
Rated impulse strength U
imp
kV 6
Utilization category
• IEC 60 947-2 (circuit breaker) A
• IEC 60 947-4-1 (motor starter) AC-3
CLASS In acc. with IEC 60 947-4-1 10 10 10/20 10/20
Direct current short-circuit breaking capacity (time constant τ = 5 ms)
(time constant t = 5 ms)
• 1 conducting path 150 VDC kA 10
• 2 conducting paths in series 300 VDC kA 10
• 3 conducting paths in series 450 VDC kA 10
Power loss (Pv) per circuit breaker I
n
-> to 1.25 A W 5 — — —
Depends on rated current I
n
I
n
-> 1.6 A to 6.3 A W 6 — — —
(Upper setting range) I
n
-> 8 A to 12 A W 7 — — —
I
n
-> to 0.63 A W — 5 — —
R
per conducting path
= P/I
2
×3 I
n
-> 0.8 A to 6.3 A W — 6 — —
I
n
-> 8 A to 16 A W — 7 — —
I
n
-> 20 A to 25 A W — 8 — —
I
n
-> to 25 A W — — 12 —
I
n
-> 32 A W — — 15 —
I
n
-> 40 A to 50 A W — — 20 —
I
n
-> to 63 A W — — — 20
I
n
-> 75 A and 90 A W — — — 30
I
n
-> to 100 A W — — — 38