Brochure
Table Of Contents
- 2 3RV1 Circuit Breaker/MSP 1)
- 2.1 Specifications/regulations/approvals
- 2.2 Device description
- 2.3 Application and areas of use
- 2.4 Accessories
- 2.4.1 Attachable accessories: Overview
- 2.4.2 Auxiliary contacts 3RV19 01-.., alarm switch 3RV19 21-111 and auxiliary release 3RV19 .2-....
- 2.4.3 Motorized remote-control mechanism 3RV19 .6-....
- 2.4.4 Disconnecting/isolator module 3RV19 .8-1A
- 2.4.5 Thru-the door rotary operators 3RV19 .6-..
- 2.4.6 Terminals for "Combination Motor Controller Type E" in acc. with UL 508
- 2.4.7 Enclosures and mounting accessories
- 2.4.8 Busbar adapter 8US1 (Fastbus system)
- 2.4.9 Isolated 3-phase busbar system
- 2.4.10 Link module for connection to a contactor
- 2.5 Mounting and connection
- 2.6 Dimensional drawings (measurements in mm)
- 2.7 Technical specifications
- 2.7.1 General specifications
- 2.7.2 Permissible rating of approved devices for North America, u s
- 2.7.3 Short-circuit breaking capacity Icn in acc. with IEC 60 947-2
- 2.7.4 Limiter function with standard devices for 500 VAC and 690 VAC in acc. with IEC 60 947-2
- 2.7.5 Characteristics
- 2.7.6 Installation guidelines
- 2.8 Application notes for the use of 3RV1 downstream from frequency converters/ inverter with pulsing voltage
Circuit Breaker/MSP 3RV1
SIRIUS System Manual
GWA 4NEB 430 0999-02 DS 01
2-49
2.5.2 Connection
Tools The following items are required to connect the circuit breakers/MSPs:
• Frame sizes S00 to S2: Pozidriv 2 screwdriver
• Frame size S3: Allen key (4 mm)
Conductor cross-sec-
tions
The typical SIRIUS conductor cross-sections apply (see Section 1.5.2 "Con-
ductor cross-sections").
Screw-type terminals 3RV1 circuit breakers/MSPs with frame sizes S00 and S0 have terminals
with captive screws and terminal washers that enable you to connect
2 conductors, even if they have different cross-sections.
The box terminals of the circuit breakers/MSPs of frame sizes S2 and S3 can
also take 2 conductors with different cross-sections. With the exception of
circuit breakers/MSPs of frame size S3, which have terminal screws with a
4 mm Allen screw, all the terminal screws can be tightened using a standard
screwdriver or a Pozidriv screwdriver (size 2).
You can remove the box terminals from circuit breakers/MSPs with a frame
size of S3 to connect conductors with ring-tongue or connecting bars. A ter-
minal cover is available as shock protection and to ensure that you comply
with the required creepages and clearances when the box terminals are
removed.
Soldering pin connec-
tor
Circuit breakers/MSPs in frame size S00 can be soldered onto printed circuit
boards by means of a soldering pin connector. A soldering pin connector is
available for the main contacts only (3RV19 18-5A) or for the main contacts
and the transverse auxiliary contacts 1NO +1NC (3RV19 18-5B).