Brochure
Table Of Contents
- 2 3RV1 Circuit Breaker/MSP 1)
- 2.1 Specifications/regulations/approvals
- 2.2 Device description
- 2.3 Application and areas of use
- 2.4 Accessories
- 2.4.1 Attachable accessories: Overview
- 2.4.2 Auxiliary contacts 3RV19 01-.., alarm switch 3RV19 21-111 and auxiliary release 3RV19 .2-....
- 2.4.3 Motorized remote-control mechanism 3RV19 .6-....
- 2.4.4 Disconnecting/isolator module 3RV19 .8-1A
- 2.4.5 Thru-the door rotary operators 3RV19 .6-..
- 2.4.6 Terminals for "Combination Motor Controller Type E" in acc. with UL 508
- 2.4.7 Enclosures and mounting accessories
- 2.4.8 Busbar adapter 8US1 (Fastbus system)
- 2.4.9 Isolated 3-phase busbar system
- 2.4.10 Link module for connection to a contactor
- 2.5 Mounting and connection
- 2.6 Dimensional drawings (measurements in mm)
- 2.7 Technical specifications
- 2.7.1 General specifications
- 2.7.2 Permissible rating of approved devices for North America, u s
- 2.7.3 Short-circuit breaking capacity Icn in acc. with IEC 60 947-2
- 2.7.4 Limiter function with standard devices for 500 VAC and 690 VAC in acc. with IEC 60 947-2
- 2.7.5 Characteristics
- 2.7.6 Installation guidelines
- 2.8 Application notes for the use of 3RV1 downstream from frequency converters/ inverter with pulsing voltage
Circuit Breaker/MSP 3RV1
SIRIUS System Manual
2-48 GWA 4NEB 430 0999-02 DS 01
2.5 Mounting and connection
2.5.1 Installation
Mounting position You can install the 3RV1 circuit breakers/MSPs in almost any position.
Snap-on mounting The circuit breakers/MSPs are mounted by snapping them onto 35 mm rails
that comply with DIN EN 50 022. The circuit breakers/MSPs with a frame
size of S3 require a rail with an installation height of 15 mm. Alternatively,
they can also be snapped onto 75 mm rails.
Fig. 2-34: Mounting the circuit breakers/MSPs onto the rail
Panel mounting The circuit breakers/MSPs can be attached to a flat surface with 2 screws.
For circuit breakers/MSPs in frame sizes S00 and S0, two push-in lugs
(3RB1900-0B) (pack of 10) are also required.
Circuit breakers/MSPs in frame sizes S2 and S3 can be screwed directly
onto a base plate.
Fig. 2-35: Screw-on mounting of the 3RV1 (example: frame size S00)
S00
RV-00298
1
2
1
1
2
DIN EN 50022/23
S3
DIN EN 50022
RV-00226
3RB19 00-0B