Brochure
Table Of Contents
- 2 3RV1 Circuit Breaker/MSP 1)
- 2.1 Specifications/regulations/approvals
- 2.2 Device description
- 2.3 Application and areas of use
- 2.4 Accessories
- 2.4.1 Attachable accessories: Overview
- 2.4.2 Auxiliary contacts 3RV19 01-.., alarm switch 3RV19 21-111 and auxiliary release 3RV19 .2-....
- 2.4.3 Motorized remote-control mechanism 3RV19 .6-....
- 2.4.4 Disconnecting/isolator module 3RV19 .8-1A
- 2.4.5 Thru-the door rotary operators 3RV19 .6-..
- 2.4.6 Terminals for "Combination Motor Controller Type E" in acc. with UL 508
- 2.4.7 Enclosures and mounting accessories
- 2.4.8 Busbar adapter 8US1 (Fastbus system)
- 2.4.9 Isolated 3-phase busbar system
- 2.4.10 Link module for connection to a contactor
- 2.5 Mounting and connection
- 2.6 Dimensional drawings (measurements in mm)
- 2.7 Technical specifications
- 2.7.1 General specifications
- 2.7.2 Permissible rating of approved devices for North America, u s
- 2.7.3 Short-circuit breaking capacity Icn in acc. with IEC 60 947-2
- 2.7.4 Limiter function with standard devices for 500 VAC and 690 VAC in acc. with IEC 60 947-2
- 2.7.5 Characteristics
- 2.7.6 Installation guidelines
- 2.8 Application notes for the use of 3RV1 downstream from frequency converters/ inverter with pulsing voltage
3RV1 Circuit Breaker/MSP
SIRIUS System Manual
2-44 GWA 4NEB 430 0999-02 DS 01
2.4.9 Isolated 3-phase busbar system
For 3RV1 frame sizes S00, S0, and S2, 3-phase busbars can be used to
quickly and easily provide line side feeding when mounting circuit breakers/
MSPs on to DIN rail. There is only one power supply, via a feed-in terminal.
The 3-phase busbar systems are safe from fingers and are shock protected
DIN VDE 0106 Teil 100. They are rated for the short-circuit stress that can
occur on the output side of the connected circuit breakers/MSPs.
Fig. 2-31: 3-phase busbar system (example: Frame size S00)
Rated operational
voltage/current
Versions
The 3-phase busbars take 2 to 5 circuit breakers/MSPs, depending on the
model. There are busbars with more generous spacing for circuit breakers/
MSPs with accessories attached on the side
3-phase busbar
3RV19 15-1CB
Protective cap
3RV19 15-6AB
Feeder lugs, connecton from
below
3RV19 15-5B
Feeder lugs, connecton from
above
(3RV1915-5A))
Spacer
Rated operational voltage
690 V
Rated current Frame sizes S00, S0: 63 A
Frame size S2: 108 A
Table 2-16: Rated operational voltage/current
Frame size
of the
circuit
breaker/
MSP
Spacing Models
S00, S0 45 mm For 2, 3, 4, or 5 circuit breakers/MSPs
55 mm For 2, 3, 4, or 5 circuit breakers/MSP + acc.
63 mm For 2 or 4 circuit breakers/MSPs + accessories
S2 55 mm For 2, 3, or 4 circuit breakers/MSPs
75 mm For 2, 3, or 4 circuit breakers/MSPs + accesso-
ries
Table 2-17: Types of 3-phase busbars