Brochure
Table Of Contents
- 2 3RV1 Circuit Breaker/MSP 1)
- 2.1 Specifications/regulations/approvals
- 2.2 Device description
- 2.3 Application and areas of use
- 2.4 Accessories
- 2.4.1 Attachable accessories: Overview
- 2.4.2 Auxiliary contacts 3RV19 01-.., alarm switch 3RV19 21-111 and auxiliary release 3RV19 .2-....
- 2.4.3 Motorized remote-control mechanism 3RV19 .6-....
- 2.4.4 Disconnecting/isolator module 3RV19 .8-1A
- 2.4.5 Thru-the door rotary operators 3RV19 .6-..
- 2.4.6 Terminals for "Combination Motor Controller Type E" in acc. with UL 508
- 2.4.7 Enclosures and mounting accessories
- 2.4.8 Busbar adapter 8US1 (Fastbus system)
- 2.4.9 Isolated 3-phase busbar system
- 2.4.10 Link module for connection to a contactor
- 2.5 Mounting and connection
- 2.6 Dimensional drawings (measurements in mm)
- 2.7 Technical specifications
- 2.7.1 General specifications
- 2.7.2 Permissible rating of approved devices for North America, u s
- 2.7.3 Short-circuit breaking capacity Icn in acc. with IEC 60 947-2
- 2.7.4 Limiter function with standard devices for 500 VAC and 690 VAC in acc. with IEC 60 947-2
- 2.7.5 Characteristics
- 2.7.6 Installation guidelines
- 2.8 Application notes for the use of 3RV1 downstream from frequency converters/ inverter with pulsing voltage
3RV1 Circuit Breaker/MSP
SIRIUS System Manual
2-34 GWA 4NEB 430 0999-02 DS 01
2.4.6 Terminals for "Combination Motor Controller Type E" in acc. with UL 508
Since July 16, 2001, 1 inch air clearance and 2 inch creepage distance is
required for "Combination Motor Controller Type E" on the input side in acc.
with UL 508. For the 3RV10 circuit breakers/MSPs frame size S0 use termi-
nal block 3RV1928-1H and for frame sizes S3 use terminal block
3RT1946-4GA07. The 3RV10 in frame size S2 complies with the required air
clearance and creepage distance without a terminal block.
These terminal blocks cannot be used in the S0 frame size at the same time
as the 3RV19.5 3-phase busbars or in the S3 frame size at the same time as
a transverse auxiliary switch.
Attention
Terminal blocks are not required for use in acc. with CSA.
Fig. 2-21: Terminals for "Combination Motor Controller Type E"
3RV19 28-1H
Self-Protected
Combination
Controller Type E
3RT19 46-4GA07
1
2
S3
S0