Brochure
Table Of Contents
- 2 3RV1 Circuit Breaker/MSP 1)
- 2.1 Specifications/regulations/approvals
- 2.2 Device description
- 2.3 Application and areas of use
- 2.4 Accessories
- 2.4.1 Attachable accessories: Overview
- 2.4.2 Auxiliary contacts 3RV19 01-.., alarm switch 3RV19 21-111 and auxiliary release 3RV19 .2-....
- 2.4.3 Motorized remote-control mechanism 3RV19 .6-....
- 2.4.4 Disconnecting/isolator module 3RV19 .8-1A
- 2.4.5 Thru-the door rotary operators 3RV19 .6-..
- 2.4.6 Terminals for "Combination Motor Controller Type E" in acc. with UL 508
- 2.4.7 Enclosures and mounting accessories
- 2.4.8 Busbar adapter 8US1 (Fastbus system)
- 2.4.9 Isolated 3-phase busbar system
- 2.4.10 Link module for connection to a contactor
- 2.5 Mounting and connection
- 2.6 Dimensional drawings (measurements in mm)
- 2.7 Technical specifications
- 2.7.1 General specifications
- 2.7.2 Permissible rating of approved devices for North America, u s
- 2.7.3 Short-circuit breaking capacity Icn in acc. with IEC 60 947-2
- 2.7.4 Limiter function with standard devices for 500 VAC and 690 VAC in acc. with IEC 60 947-2
- 2.7.5 Characteristics
- 2.7.6 Installation guidelines
- 2.8 Application notes for the use of 3RV1 downstream from frequency converters/ inverter with pulsing voltage
3RV1 Circuit Breaker/MSP
SIRIUS System Manual
2-28 GWA 4NEB 430 0999-02 DS 01
2.4.5 Thru-the door rotary operators 3RV19 .6-..
Thru-the-door rotary operators are available for frame sizes S0, S2, and S3.
They consist of a lockable rotary handle with a detachable door coupling, an
extension shaft, and a connector for the switch drive.
There are two basic designs available. The thru-the-door rotary operator
3RV19 26-0. for standard applications and the thru-the-door rotary operator
3RV19 .6-2. for harsh conditions. Both designs have an IP65 rating and can
be locked in the OFF-position with up to three padlocks.
Both operators are available with either black/grey and/or red/yellow for
emergency-stop handle styles.
The thru-the-door rotary operator for harsh conditions also meet the discon-
nection requirements according to IEC 60 947-2.