Brochure
Table Of Contents
- 2 3RV1 Circuit Breaker/MSP 1)
- 2.1 Specifications/regulations/approvals
- 2.2 Device description
- 2.3 Application and areas of use
- 2.4 Accessories
- 2.4.1 Attachable accessories: Overview
- 2.4.2 Auxiliary contacts 3RV19 01-.., alarm switch 3RV19 21-111 and auxiliary release 3RV19 .2-....
- 2.4.3 Motorized remote-control mechanism 3RV19 .6-....
- 2.4.4 Disconnecting/isolator module 3RV19 .8-1A
- 2.4.5 Thru-the door rotary operators 3RV19 .6-..
- 2.4.6 Terminals for "Combination Motor Controller Type E" in acc. with UL 508
- 2.4.7 Enclosures and mounting accessories
- 2.4.8 Busbar adapter 8US1 (Fastbus system)
- 2.4.9 Isolated 3-phase busbar system
- 2.4.10 Link module for connection to a contactor
- 2.5 Mounting and connection
- 2.6 Dimensional drawings (measurements in mm)
- 2.7 Technical specifications
- 2.7.1 General specifications
- 2.7.2 Permissible rating of approved devices for North America, u s
- 2.7.3 Short-circuit breaking capacity Icn in acc. with IEC 60 947-2
- 2.7.4 Limiter function with standard devices for 500 VAC and 690 VAC in acc. with IEC 60 947-2
- 2.7.5 Characteristics
- 2.7.6 Installation guidelines
- 2.8 Application notes for the use of 3RV1 downstream from frequency converters/ inverter with pulsing voltage
3RV1 Circuit Breaker/MSP
SIRIUS System Manual
2-16 GWA 4NEB 430 0999-02 DS 01
2.3.6 Switching direct current
The 3RV1 circuit breaker/MSPs for alternating current are suitable for
switching direct current. However, you must note the maximum permissible
DC voltage per conducting path. In the case of higher voltages, series con-
nection of 2 or 3 conducting paths is required.
Response thresholds The response thresholds of the overload releases remain unchanged. The
response thresholds of the short-circuit releases are increased with direct
current by approximately 40 %.
The following table lists suggestions for switching direct current:
Double ground fault Note
In the case of the circuit with 2-pole switching and an ungrounded system, it
is assumed that even in the event of a double ground fault that bridges two
contacts, safe disconnection still occurs.
2.3.7 Main and emergency stop switches
Since the circuit breaker/MSPs meet the requirements for disconnectors in
acc. with IEC 60947-3 and the additional test requirements for circuit
breaker/MSPs with disconnector features in acc. with IEC 60947-2, they can
be used with the appropriate accessories as main and emergency stop
switches. They must also comply with DIN VDE 0113.
Suggestion
circuit
breaker/
MSP
Frame
size
Max.
permissible
direct voltage
E
I
Meaning
3RV1. S00 to
S3
DC 150 V 2-pole switching
Ungrounded system
If a ground fault can be excluded, or if every
ground fault is immediately corrected
(ground-fault monitoring), the maximum per-
missible DC voltage can be tripled.
3RV1. S00 to
S3
DC 300 V 2-pole switching
Grounded system
The grounded pole must always be assigned
to the individual conducting path so that in
the event of a ground fault there are always
2 conducting paths in series.
3RV1. S00 to
S3
DC 450 V 1-pole switching
Grounded system
3 conducting paths in series.
The grounded pole should be assigned to
the non switched conducting path.
Table 2-4: Suggestions for switching direct current
L-
M
L
+
L-
L
M
+
L-L
M
+










