Brochure
Table Of Contents
- 2 3RV1 Circuit Breaker/MSP 1)
- 2.1 Specifications/regulations/approvals
- 2.2 Device description
- 2.3 Application and areas of use
- 2.4 Accessories
- 2.4.1 Attachable accessories: Overview
- 2.4.2 Auxiliary contacts 3RV19 01-.., alarm switch 3RV19 21-111 and auxiliary release 3RV19 .2-....
- 2.4.3 Motorized remote-control mechanism 3RV19 .6-....
- 2.4.4 Disconnecting/isolator module 3RV19 .8-1A
- 2.4.5 Thru-the door rotary operators 3RV19 .6-..
- 2.4.6 Terminals for "Combination Motor Controller Type E" in acc. with UL 508
- 2.4.7 Enclosures and mounting accessories
- 2.4.8 Busbar adapter 8US1 (Fastbus system)
- 2.4.9 Isolated 3-phase busbar system
- 2.4.10 Link module for connection to a contactor
- 2.5 Mounting and connection
- 2.6 Dimensional drawings (measurements in mm)
- 2.7 Technical specifications
- 2.7.1 General specifications
- 2.7.2 Permissible rating of approved devices for North America, u s
- 2.7.3 Short-circuit breaking capacity Icn in acc. with IEC 60 947-2
- 2.7.4 Limiter function with standard devices for 500 VAC and 690 VAC in acc. with IEC 60 947-2
- 2.7.5 Characteristics
- 2.7.6 Installation guidelines
- 2.8 Application notes for the use of 3RV1 downstream from frequency converters/ inverter with pulsing voltage
3RV1 Circuit Breaker/MSP
SIRIUS System Manual
GWA 4NEB 430 0999-02 DS 01
2-15
Auxiliary switch func-
tions
The circuit breaker/MSP used for fuse monitoring can be equipped with a
transverse or lateral auxiliary switch (Section 2.4, Accessories). The auxiliary
switch reports the tripping of the circuit breaker/MSP and thus the failure of
the fuse and initiates an all-pole disconnection of the problem circuit by a
corresponding switching device.
Safety sign
Note
When fuses used for isolation purposes are monitored, a warning sign must
be put up next to them. Via the parallel-switched voltage circuit of the moni-
toring facility, voltage may get into the area that is supposed to be isolated if
the monitoring equipment has not been disconnected.
We suggest the following text for the warning:
Voltages The 3RV16 11-0DB10 circuit breaker/MSP is suitable for fuse monitoring in
the following voltage ranges:
• 24 to 690 VAC, 50/60
Hz
• 24 to 250 VDC, 100 to 600 VDC
Switching capacity I
CN
100 kA
Circuit diagrams
Fig. 2-9: Circuit diagrams of circuit breaker/MSPs for fuse monitoring
Parallel cables/meshed
networks
Attention
In the case of parallel cables and meshed networks, a tripping operation and
signal only occurs when the voltage difference at the circuit breaker/MSP is
at least 24 V.
Attention
To ensure isolation, also disconnect
the fuse-monitoring device with the
item designation............
U
e
AC 24 ... 690V DC 24 ... 250V DC 100 ... 600V
I
»
I
»
I
»
I
»
I
»
I
»
I»I» I»