Submittal Sheet

● in networks with grounded star point between
main and auxiliary circuit
400V
protection class IP
● on the front
IP20
● of the terminal
IP00
shock resistance
● acc. to IEC 60068-2-27
25g / 11 ms Sinus
mechanical service life (switching cycles)
● of the main contacts typical
25000
● of auxiliary contacts typical
25000
electrical endurance (switching cycles)
● typical
25000
reference code acc. to DIN EN 81346-2 Q
Ambient conditions
● installation altitude at height above sea level
maximum
2000m
ambient temperature
● during operation
-20...+60°C
● during storage
-50...+80°C
● during transport
-50...+80°C
temperature compensation -20...+60°C
relative humidity during operation 10...95%
Main circuit
number of poles for main current circuit 3
adjustable pick-up value current of the current-
dependent overload release
45...63A
operating voltage
● rated value
690V
● at AC-3 rated value maximum
690V
operating frequency rated value 50...60Hz
operating current rated value 63A
operating current
● at AC-3
— at 400 V rated value
63A
operating power
● at AC-3
— at 230 V rated value
18500W
— at 400 V rated value
30000W
— at 500 V rated value
37000W
— at 690 V rated value
55000W
operating frequency
● at AC-3 maximum
151/h
3RV2042-4JB10 Subject to change without notice