Submittal Sheet
— at 460/480 V rated value
10hp
Short-circuit protection
Product function Short circuit protection Yes
Design of the short-circuit trip magnetic
Design of the fuse link for IT network for short-circuit
protection of the main circuit
● at 400 V
gL/gG 63 A
● at 500 V
gL/gG 50 A
● at 690 V
gL/gG 40 A
Installation/ mounting/ dimensions
Mounting position any
Mounting type screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
Height 97mm
Width 45mm
Depth 96mm
Required spacing
● with side-by-side mounting
— forwards
0mm
— Backwards
0mm
— upwards
50mm
— downwards
50mm
— at the side
0mm
● for grounded parts
— forwards
0mm
— Backwards
0mm
— upwards
50mm
— at the side
30mm
— downwards
50mm
● for live parts
— forwards
0mm
— Backwards
0mm
— upwards
50mm
— downwards
50mm
— at the side
30mm
Connections/Terminals
Product function
● removable terminal for auxiliary and control
circuit
No
Type of electrical connection
● for main current circuit
screw-type terminals
3RV2021-4AA10 Subject to change without notice
Page 4/
9
05/28/2018 © Copyright Siemens