Submittal Sheet

● on the front
IP20
● of the terminal
IP20
Shock resistance
● acc. to IEC 60068-2-27
25g / 11 ms
Mechanical service life (switching cycles)
● of the main contacts typical
100000
● of auxiliary contacts typical
100000
Electrical endurance (switching cycles)
● typical
100000
Type of protection Increased safety
Certificate of suitability ATEX Yes
Protection against electrical shock finger-safe
Reference code acc. to DIN EN 81346-2 Q
Ambient conditions
Installation altitude at height above sea level
● maximum
2000m
Ambient temperature
● during operation
-20...+60°C
● during storage
-50...+80°C
● during transport
-50...+80°C
Temperature compensation -20...+60°C
Relative humidity during operation 10...95%
Main circuit
Number of poles for main current circuit 3
Adjustable pick-up value current of the current-
dependent overload release
10...16A
Operating voltage
● rated value
690V
● at AC-3 rated value maximum
690V
Operating frequency rated value 50...60Hz
Operating current rated value 16A
Operating current
● at AC-3
— at 400 V rated value
16A
Operating power
● at AC-3
— at 230 V rated value
4000W
— at 400 V rated value
7500W
— at 500 V rated value
7500W
— at 690 V rated value
11000W
Operating frequency
● at AC-3 maximum
151/h
3RV2021-4AA10 Subject to change without notice
Page 2/
9