Submittal Sheet

Ambient temperature
● during operation
-20...+60°C
● during storage
-50...+80°C
● during transport
-50...+80°C
Main circuit
Number of poles for main current circuit 3
Adjustable pick-up value current of the current-
dependent overload release
1.8...2.5A
Operating voltage
● rated value
690V
● at AC-3 rated value maximum
690V
Operating current
● at AC-3
— at 400 V rated value
2.5A
Operating power
● at AC-3
— at 400 V rated value
0.75kW
Operating frequency
● at AC-3 maximum
151/h
Auxiliary circuit
Number of CO contacts
● for auxiliary contacts
0
Protective and monitoring functions
Product function
● Ground fault detection
No
● Phase failure detection
Yes
Trip class CLASS 10
Maximum short-circuit current breaking capacity (Icu)
● at AC at 240 V rated value
100kA
● at AC at 400 V rated value
100kA
● at AC at 500 V rated value
100kA
● at AC at 690 V rated value
8kA
Short-circuit protection
Design of the overcurrent release and short-circuit
release
thermomagnetic
Installation/ mounting/ dimensions
Mounting position any
Mounting type screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 50022
Height 97mm
Width 45mm
3RV1021-1CA10 Subject to change without notice
Page 2/
5
11/27/2017 © Copyright Siemens