Submittal Sheet
— at 440 V rated value
0.6A
— at 600 V rated value
0.35A
Operating power
● at AC-1
— at 230 V rated value
26kW
— at 230 V at 60 °C rated value
23kW
— at 400 V rated value
46kW
— at 400 V at 60 °C rated value
39kW
— at 690 V rated value
79kW
— at 690 V at 60 °C rated value
68kW
● at AC-2 at 400 V rated value
22kW
● at AC-3
— at 230 V rated value
15kW
— at 400 V rated value
22kW
— at 500 V rated value
30kW
— at 690 V rated value
22kW
Operating power for approx. 200000 operating cycles
at AC-4
● at 400 V rated value
12.6kW
● at 690 V rated value
18.2kW
Thermal short-time current limited to 10 s 420A
Power loss [W] at AC-3 at 400 V for rated value of
the operating current per conductor
4W
No-load switching frequency
● at AC
50001/h
Operating frequency
● at AC-1 maximum
10001/h
● at AC-2 maximum
6001/h
● at AC-3 maximum
8001/h
● at AC-4 maximum
2501/h
Control circuit/ Control
Type of voltage of the control supply voltage AC
Control supply voltage at AC
● at 50 Hz rated value
24V
● at 60 Hz rated value
24V
Operating range factor control supply voltage rated
value of magnet coil at AC
● at 50 Hz
0.8...1.1
● at 60 Hz
0.85...1.1
Apparent pick-up power of magnet coil at AC
● at 50 Hz
210V·A
● at 60 Hz
188V·A
3RT2036-1AC20 Subject to change without notice
Page 4/
10
11/28/2017 © Copyright Siemens