Voltage ranges The following graphic shows you the voltage ranges for electronic control-
lers and drives of contactors and contactor relays with a rated control supply
voltage of U
s
=24VDC:
Fig. 3-24: Contactor relays: voltage ranges
Auxiliary contact blocks Auxiliary contact blocks can be built on as follows:
Frame size S00: none
Frame size S0: a maximum of two 1-pole auxiliary contact blocks
Power consumption Variant 1: The power input of the magnet coils for contactor relays in frame
size S00 is 2.3 W at 24 VDC (operating range: 0.7 to 1.25 x U
S
).
Variant 2: Contactor relays with reduced coil performance in frame size
S00, P = 1.4 W at 24 VDC (operating range: 0.85 to 1.85 U
S
).
The power input of magnet coils for contactor relays in frame size S0 is
4.2 W at 24 VDC (operating range: 0.7 to 1.25 x U
S
).
30
24
17
1.25 U
s
1.0 U
s
0.7 U
s
1.2 x U
s
1.1 x U
s
1.2 x U
s
1.25 x U
s
0.85 x U
s
0.85 x U
s
0.72 x U
s
0.7 x U
s
28.8 V
20.4 V
26.4 V
20.4 V
28.8 V
17.4 V
30 V
17 V
U
Supply voltage
range
Electronic control-
lers in acc. with
DIN 19340
Operating range
for contactors in
acc. with
VDE 0660 part 102
Voltage range of
electronic outputs
at
<
3 V internal
voltage drop
Operating range of
contactors for
electronic control-
lers