3RT1 contactors/3RH1 control relays
SIRIUS System Manual
3-42 GWA 4NEB 430 0999-02 DS 01
Important
When switching banks of capacitors make sure that you adhere to the spec-
ified minimum inductance between the capacitors connected in parallel.
3RT10. capacitor
switching capacity
The normal 3RT10 contactors for switching motors also have a certain
capacitor switching capacity. Details of this can be found in
Section 3.7, Technical specifications: Utilization category AC-6b, switching of
individual capacitors and switching of low-inductance three-phase capaci-
tors. The tables contain information on the switching of individual capacitors
and the switching of banks of capacitors.
Operation Caution
Only switch to discharged capacitors! Do not carry out a function test by
hand.
The precharging resistors must not be removed as this will damage the con-
tact pieces in circuits with a load.
Circuit diagram S00 S0 and S3
Fig. 3-19: Capacitor contactors, circuit diagram
L1 L2 L3
A1
F0
13
5
24
6
A2
43
44
C1
L1 L2 L3
A1
NSB01382
F0
13
5
24
6
A2
13
14
C1
51
52