User Guide

3RT1 contactors/ 3RH1 control relays
SIRIUS System Manual
GWA 4NEB 430 0999-02 DS 01
3-19
Power supply The control voltage Us needs to be applied to the A1/A2 terminals of the
side mounted electronic module, this supplies power for the magnetic coil
and the remaining lifetime indication.
Control inputs The control inputs for the contactor are connected on the 7-pole terminal
block (The terminals supplied with the unit have Cage Clamp-Technology).
Switching from Auto-
matic-/Manual control
Control of the contactor can be switched from automatic control to manual
control using the input terminals H1/H2. Manual control may be required at
start-up or to switch the contactor after loss of power on a PLC or
SIMOCODE-DP device.
Control with a PLC with
24 V DC
Control using relay out-
puts
Control directly from a PLC with
24 V DC without a coupling
device
via PLC -control input IN+/IN–
(EN 61 131-2/Type 2)
Current consumption 30 mA
Operational range17 to 30 V DC
Note
H2 and A1 are internally con-
nected and therefore have the
same voltage potential
Control using relay outputs, for
example from:
•PLC
SIMOCODE-DP (3UF5)
Relay outputs can control the
contactor through the H1/H2 ter-
minals.
The relay contacts are loaded to
about 5 mA plus the control volt-
age applied at the A1/A2 termi-
nals
Note
H2 and A1 are internally con-
nected and therefore have the
same voltage potential
e.g.
SIMOCODE-DP
others
PLC
Signal
Residual service live 20%
L1/L+
N/L-
A1 A2
H1
H2
R1
R2
IN
IN
S1
S2
3RT1...-.P
NSB01147a
1 2
PROFIBUS-DP
1
2
Electronic module of 3RT1...-.P contactor
Plug in connection, 7-pole
S1
S2
Changeover switch from automatic
control, e.g., via SIMOCODE-DP or
PLC relay output on-site control option
On-site control option