Product Overview

3RT1 contactors/3RH1 control relays
SIRIUS System Manual
GWA 4NEB 430 0999-02 DS 01
3-109
Description The connection of the main conducting path to the EMC suppression mod-
ule reduces the contact sparking that is responsible for contact erosion and
many of the disturbances, which in turn supports an EMC-compatible config-
uration.
Mode of operation The EMC suppression module reduces through 3 phases the radio-fre-
quency parts and the voltage peaks. The advantages of this are as follows:
Longer service life of the contact pieces
Higher operational reliability and high system availability
A fine grading within the performance class is not required because smaller
motors have greater inductance due to their construction, and one EMC sup-
pression module is thus sufficient for all non-stabilized drives up to 5.5 kW.
Variants Two electrical variants are available:
•RC circuit
Varistor switching
Circuit diagrams
Fig. 3-70: circuit diagrams
Installation
Fig. 3-71: EMC suppression module
L1
L3
L2
R_L1
R_L2
R_L3
C_L1
C_L2
C_L3
U
U
U
M
3~
M
3~
2T1 4T2 6T3 2T1 4T2 6T3
V_L1
V_L2
V_L3
The EMC suppression module is
attached to the underside of the con-
tactor. To do this, hook the EMC sup-
pression module with both hooks onto
the contactor, and push it upward until
the connection pins of the EMC mod-
ule are firmly in place in the terminal
openings of the contactor.
1
2
3RT19 16-1P..