Product Overview
Table Of Contents
- 3RT1 contactors/3RH1 control relays
- 3.4 Accessories
- 3.4.1 Attachable auxiliary switches for extending the auxiliary contacts
- 3.4.2 Time-delay auxiliary switches
- 3.4.3 Solid-state time relay blocks with semiconductor output
- 3.4.4 Additional load module (3RT1916-1GA00)
- 3.4.5 Coupling element for frame sizes S0 to S3 (3RH1924-1GP11)
- 3.4.6 Surge suppression
- 3.4.7 Other accessories
- 3.4.7.1 LED module for indicating contactor control (3RT1926-1QT00)
- 3.4.7.2 Auxiliary connecting lead terminal, 3-pole for frame size S3 (3RT19 46-4F)
- 3.4.7.3 Box terminal blocks
- 3.4.7.4 EMC interference suppression module (3RT1916-1P..)
- 3.4.7.5 Soldering pin adapter for frame size S00 (3RT19 16-4KA.)
- 3.4.7.6 Paralleling links (3RT19 .6-4B.31)
- 3.4.7.7 Sealing cover (3RT19 .6-4MA10)
- 3.4.7.8 Terminal covers for frame sizes S2 to S12
- 3.4 Accessories
3RT1 contactors/3RH1 control relays
SIRIUS System Manual
3-108 GWA 4NEB 430 0999-02 DS 01
3.4.7.3 Box terminal blocks
Main cable connec-
tions
Other than the 3RT1054 (55 kW/400 V/AC-3), that can optionally come with
the box terminal block 3RT1955-4G, the S6 to S12 contactors come with
busbar connection. For the direct connection of round cables or ribbon cable
box terminal blocks (as accessories) can be used for frame sizes S6 to S12.
Control power take off With the box terminal blocks for frame size S6 there is space to use the con-
trol power take off terminal 3TX7500-0A.
The box terminal blocks for S10/12 have per main cable connection also a
connection for control power take off..
Fig. 3-69: Control power take off with the box terminal blocks
3.4.7.4 EMC interference suppression module (3RT1916-1P..)
In the case of motors or various inductive loads, back-e.m.f (electromotive
force) is produced when disconnected. This can produce voltage peaks of up
to 4000 V with a frequency range of 1 kHz to 10 MHz and a rate of voltage
variation of 0.1 to 20 V/ns.
Capacitive coupling to various analog and digital signals makes suppression
necessary in the load circuit.
1 / 4
5
2
3
3TX7500-0A
3RT1956-4EA2
1
3
4
2
5
3RT1966-4EA2
Frame size box terminal block Terminal cover
connection cross-section Order No. Control power take off Order No.
S6 up to 70 mm
2
3RT1955-4G with 3TX7500-0A 3RT1956-4EA2
up to120 mm
2
3RT1956-4G
S10 and S12 up to 240 mm
2
3RT1966-4G integrated 3RT1966-4EA2