Product Overview

3RT1 contactors/3RH1 control relays
SIRIUS System Manual
GWA 4NEB 430 0999-02 DS 01
3-103
Varisto r
Fig. 3-64: Circuit with a varistor (AC/DC operation)
This is what happens when a coil is de-energized that is connected to a
varistor (voltage-dependent resistor):
Voltage peaks still occur. They are cut off at approximately 400 V and have a
shorter overall duration (approximately 50 µs).
(Note: The oscillogram is cut off, and the voltage is reduced to zero after
approximately 3 ms.)
A varistor is suitable for AC and DC operation.
The Opening time of the contactor is extended by approximately 2 to 5 ms.
RC-Element
Fig. 3-65: Circuit with an RC element (AC/DC operation)
This is what happens when a coil is de-energized that is connected to an RC
element:
The amplitude and rate of rise of the switching overvoltage are reduced by
the capacitor. Showering arcs no longer occur. The voltage swings briefly to
400 V and then slowly drops down. This represents ideal damping.
Disadvantage: The component is larger and generally more expensive.
RC elements are suitable for AC and DC operation.
Only a minimal Opening time occurs (under 1 ms).