Product Overview
Table Of Contents
- 3RT1 contactors/3RH1 control relays
- 3.4 Accessories
- 3.4.1 Attachable auxiliary switches for extending the auxiliary contacts
- 3.4.2 Time-delay auxiliary switches
- 3.4.3 Solid-state time relay blocks with semiconductor output
- 3.4.4 Additional load module (3RT1916-1GA00)
- 3.4.5 Coupling element for frame sizes S0 to S3 (3RH1924-1GP11)
- 3.4.6 Surge suppression
- 3.4.7 Other accessories
- 3.4.7.1 LED module for indicating contactor control (3RT1926-1QT00)
- 3.4.7.2 Auxiliary connecting lead terminal, 3-pole for frame size S3 (3RT19 46-4F)
- 3.4.7.3 Box terminal blocks
- 3.4.7.4 EMC interference suppression module (3RT1916-1P..)
- 3.4.7.5 Soldering pin adapter for frame size S00 (3RT19 16-4KA.)
- 3.4.7.6 Paralleling links (3RT19 .6-4B.31)
- 3.4.7.7 Sealing cover (3RT19 .6-4MA10)
- 3.4.7.8 Terminal covers for frame sizes S2 to S12
- 3.4 Accessories
3RT1 contactors/3RH1 control relays
SIRIUS System Manual
3-100 GWA 4NEB 430 0999-02 DS 01
Technical specifications Rated voltage AC 50/60 Hz
180 V to 255 V
Rated output power 1.65 W at 230 V
Permissible contactor types 3RT1.1
3RT1.
Associated coil type P0 (230 V, 50/60 Hz)
N2 (220 V, 50/60 Hz)
P6 (220 V, 50 Hz/240 V, 60 Hz)
Operating range 0.8 to 1.1 Us
Installation The additional load is connected in parallel to the contactor coil. It has the
same construction as the surge suppressor and is attached on the front of
the contactors with or without an auxiliary switch block.
3.4.5 Coupling element for frame sizes S0 to S3 (3RH1924-1GP11)
Field of application The 3RH1924-1GP11 coupling link is intended for contactors of frame sizes
S0 to S3. It can be controlled by a programmable controller output because
the operating range of 17 to 30 VDC is permissible.
Mode of operation A contactor of frame size S0 to S3 can be controlled, for example, at 24 VDC
with a low control level (< 0.5 W) from a programmable controller output.
The control voltage for the coupling link and the rated control supply voltage
for the contactor are electrically isolated. An LED indicates the switching
state of the coupling link.
To dampen switching overvoltages of the contactor coil, a varistor is inte-
grated in the coupling link.
Installation Caution
Switch off the supply voltage applied to L1 and N before installation.
Fig. 3-61: Coupling link (frame sizes S0 to S3)
The coupling link is inserted with its
two integrated mounting pins directly
onto the coil connections of the con-
tactor.
2
1