Product Overview
Table Of Contents
- 3RT1 contactors/3RH1 control relays
- 3.4 Accessories
- 3.4.1 Attachable auxiliary switches for extending the auxiliary contacts
- 3.4.2 Time-delay auxiliary switches
- 3.4.3 Solid-state time relay blocks with semiconductor output
- 3.4.4 Additional load module (3RT1916-1GA00)
- 3.4.5 Coupling element for frame sizes S0 to S3 (3RH1924-1GP11)
- 3.4.6 Surge suppression
- 3.4.7 Other accessories
- 3.4.7.1 LED module for indicating contactor control (3RT1926-1QT00)
- 3.4.7.2 Auxiliary connecting lead terminal, 3-pole for frame size S3 (3RT19 46-4F)
- 3.4.7.3 Box terminal blocks
- 3.4.7.4 EMC interference suppression module (3RT1916-1P..)
- 3.4.7.5 Soldering pin adapter for frame size S00 (3RT19 16-4KA.)
- 3.4.7.6 Paralleling links (3RT19 .6-4B.31)
- 3.4.7.7 Sealing cover (3RT19 .6-4MA10)
- 3.4.7.8 Terminal covers for frame sizes S2 to S12
- 3.4 Accessories
3RT1 contactors/3RH1 control relays
SIRIUS System Manual
3-96 GWA 4NEB 430 0999-02 DS 01
Function diagrams
Fig. 3-53: Time-delay auxiliary switches, function diagrams (frame sizes S0 to S3)
3.4.3 Solid-state time relay blocks with semiconductor output
The solid-state time relay blocks are suitable for AC and DC operation. To
dampen switching overvoltages of the contactor coil, a varistor is inte-
grated.
Variants The following variants of the time-delay auxiliary switch are available:
• On-delay (integrated varistor)
• Off-delay with auxiliary supply (integrated varistor)
On-delay and off-delay
functions
The time-delay auxiliary switch in the on-delay or off-delay with an auxiliary
supply has the following features:
• It facilitates time-delayed functions up to 100 seconds.
• 3 individual time ranges
• Contactors with a solid-state time relay block close and open with a delay
according to the time set.
Connection: on-delay
time relay block
The on-delay time relay block is connected in series to the contactor coil;
the A1 terminal of the contactor coil must not be separately connected to
the control supply.
Connection: off-delay
time relay block
When an off-delay time relay block is attached, the contactor coil is con-
nected via the time relay block; the A1 and A2 terminals of the contactor coil
must not be separately connected to the control supply.
Conductor cross-sec-
tions
The permissible conductor cross-sections correspond to the auxiliary con-
ductor terminals of the corresponding frame size.
On-delay
1 NO and 1 NC contact
Off-delay without auxiliary supply
1 NO and 1 NC contact
Wye-delta function
1 NO contact, instantaneous
1 NO contact, delayed
t
NSK-7932
A1/A2
27/28
35/36
t
NSK-7933a
A1/A2
27/28
35/36
200 ms
>
t
NSK-7955
A1/A2
Y 27/28
D 37/38
50 ms