Submittal Sheet
Shock resistance with sine pulse
● at AC
11,8g / 5 ms, 7,4g / 10 ms
Mechanical service life (switching cycles)
● of contactor typical
10000000
● of the contactor with added electronics-
compatible auxiliary switch block typical
5000000
● of the contactor with added auxiliary switch
block typical
10000000
Equipment marking
● acc. to DIN 40719 extended according to IEC
204-2 acc. to IEC 750
K
● acc. to DIN EN 61346-2
Q
Ambient conditions
Installation altitude at height above sea level
● maximum
2000m
Ambient temperature
● during operation
-25...+60°C
● during storage
-55...+80°C
Main circuit
Number of poles for main current circuit 3
Number of NO contacts for main contacts 3
Operating voltage
● at AC-3 rated value maximum
690V
Operating current
● at AC-1 at 400 V
— at ambient temperature 40 °C rated value
40A
● at AC-1
— up to 690 V at ambient temperature 40 °C
rated value
40A
— up to 690 V at ambient temperature 60 °C
rated value
35A
● at AC-2 at 400 V rated value
9A
● at AC-3
— at 400 V rated value
9A
— at 500 V rated value
9A
— at 690 V rated value
9A
Connectable conductor cross-section in main circuit
at AC-1
● at 60 °C minimum permissible
10mm²
● at 40 °C minimum permissible
10mm²
Operating current for approx. 200000 operating
cycles at AC-4
3RT2023-1AC20 Subject to change without notice
Page 2/
11
11/29/2017 © Copyright Siemens