“Safety” Contactors
Safety rated contactors are required to
have mirrored contact construction
according to IEC 60947-4 Annex F. A
mirror contact is a Normally Closed (NC)
auxiliary contact which can not be closed
simultaneously with a Normally Open
(NO) main contact. In some industries,
such as Automotive, the auxiliary contact
blocks are required to be permanently
attached to meet the requirements of
“unitentional misuse” as specified in IEC
60292, paragraph 3.12. Tested by SUVA.
"Safety" Control Relays
Safety rated control relays are required
to have positively driven contact
elements according to IEC 60947-5-1
Annex L. Positively driven contact
elements are a combination of NO
auxiliary contacts and NC auxiliary
contacts whose construction prevents
them from being closed simultaneously.
In some industries, such as automotive,
the auxiliary contact blocks are required
to be permanently attached to meet the
requirements of "unitentional misuse" as
specified in IEC 60292, paragraph 3.12.
Tested by SUVA.
3RT202* -1AK64-3MA0 3RH22**-2BB40
IEC 60947-4-1
for contactors
IEC 60947-5-1
for control
relays
Application
Application
Frame
Size
Max.
current
Single-phase
HP ratings
Three-phase
HP ratings Auxiliary contacts
Screw
Terminals
Spring-Type
Terminals
1)
AC3 AC1
115V 220/240V
200V 230V 460V 575V
A A HP HP HP HP HP HP Ident. No. NO NC
Order No. Order No.
Contactors with permanently mounted auxiliary contact blocks
S00 6 18 ¼ ¾ 1 ½ 2 3 5 22E 2 2
3RT2015-1●●●4-3MA0 3RT2015-2●●●4-3MA0
9 22
1
3
1 2 3 5 7 ½ 22E 2 2
3RT2016-1
●●●4-3MA0 3RT2016-2
●●●4-3MA0
12 22 ½ 2 3 3 7 ½ 10 22E 2 2
3RT2017-1
●●●4-3MA0 3RT2017-2●●●4-3MA0
16 22 1 2 3 5 10 10 22E 2 2
3RT2018-1
●●●4-3MA0 3RT2018-2
●●●4-3MA0
S0 9 40 1 1 2 3 5 7 ½ 22E 2 2
3RT2023-1
●●●4-3MA0 3RT2023-2●●●4-3MA0
12 40 1 2 3 3 7 ½ 10 22E 2 2
3RT2024-1
●●●4-3MA0 3RT2024-2●●●4-3MA0
17 40 1 3 5 5 10 15 22E 2 2
3RT2025-1
●●●4-3MA0 3RT2025-2●●●4-3MA0
25 40 2 3 7 ½ 7 ½ 15 20 22E 2 2
3RT2026-1
●●●4-3MA0 3RT2026-2
●●●4-3MA0
32 50 2 5 10 10 20 25 22E 2 2
3RT2027-1
●●●4-3MA0 3RT2027-2●●●4-3MA0
38 50 3 5 10 10 25 25 22E 2 2
3RT2028-1
●●●4-3MA0 3RT2028-2
●●●4-3MA0
S2 40 60 3 7 ½ 10 15 30 40 22E 2 2
3RT2035-1
●●●4-3MA0 3RT2035-3●●●4-3MA0
50 70 3 10 15 15 40 50 22E 2 2
3RT2036-1
●●●4-3MA0 3RT2036-3●●●4-3MA0
65 80 5 10 20 20 50 50 22E 2 2
3RT2037-1
●●●4-3MA0 3RT2037-3●●●4-3MA0
80
4)
90 5 15 20 25 50 60 22E 2 2
3RT2038-1●●●4-3MA0 3RT2038-3●●●4-3MA0
S3 80 120 7 ½ 15 25 30 60 75 22E 2 2
3RT2045-1
●●●4-3MA0 3RT2045-3●●●4-3MA0
95 120 10 20 30 30 75 100 22E 2 2
3RT2046-1
●●●4-3MA0 3RT2046-3●●●4-3MA0
S6 150 185 -- 30 50 60 125 150 22E 2 2
3RT1055-6
●●●6-3PA0
185 215 -- 30 60 75 150 200 22E 2 2
3RT1056-6
●●●6-3PA0
S10 225 275 -- -- 60 75 150 200 22E 2 2
3RT1064-6
●●●6-3PA0
265 330 -- -- 75 100 200 250 22E 2 2
3RT1065-6
●●●6-3PA0
300 330 -- -- 100 125 250 300 22E 2 2
3RT1066-6
●●●6-3PA0
Control circuit coil options: Replace ●●● with the desired code
Frame Size S00 - S0 ●●● Frame Size S2 ●●● Frame Size S3 ●●● Frame Size S6 - S10 ●●●
120 V AC
AK6
120 V AC
AK6
120 V AC **
AK6
23 … 26 V UC*, conventional coil
AB3
120 V AC, integrated varistor
CK6
120 V AC w/ Varistor
CK6
24 V DC
BB4
21-27 V UC*, solid state coil
NB3
230 V AC
AP0
24 V DC w/Varistor
KB4
24 V DC w/diode assy
QB4
w/ PLC interface
24 V DC
BB4
110 … 127 V UC*, conventional coil
AF3
24 V DC, integrated varistor
DB4
**Available in 3RT1046 only
*UC coil: accepts DC voltage or
AC voltage, 40 to 60 Hz.
24 V DC, integrated diode assy.
FB4
Frame
Size
Max. current
at 240 V
2)
Rated control supply
voltage U
s
Auxiliary contacts
Screw
Terminals
3)
Spring
Terminals
3)
A Indent. No. NO NC
Order No. Order No.
Control relays with permanently mounted auxiliary contact blocks
S00-S00 10
10
10
10
110 V AC, 50 Hz / 120 V AC, 60 Hz
24 V DC
110 V AC, 50 Hz / 120 V AC, 60 Hz
24 V DC
44E
44E
62E
62E
4
4
6
6
4
4
2
2
3RH2244-1AK60
3RH2244-1BB40
3RH2262-1AK60
3RH2262-1BB40
3RH2244-2AK60
3RH2244-2BB40
3RH2262-2AK60
3RH2262-2BB40
For other voltages see page 2/49.
For accessories, see pages 2/73-2/78.
For spare parts, see pages
2/94
-
2/97
.
For technical data, see pages
2/121
-
2/142
.
For description, see pages
2/104
-2/105.
For int. circuit diagrams, see page
2/190-
2/196.
For dimension drawings, see pages
2/209
-
2/215
.
1) All terminals are spring loaded on frame size S00 and S0.
Only the coil and auxiliary contact terminals are spring
loaded on frame sizes S2 & S3.
2) For AC-15/AC-14, max current for front mounted auxiliary contacts = 6 A.
3) The 3RH22 control relays are also available with ring lug terminals. Replace
the 8th digit of the order number with a “4”, e. g. 3RH2244-4AK60
4) Max UL FLA = 65A at 460V
Contactors and Contactor Assemblies
Contactors & Relays for Safety Applications
3RT safety contactors, 3RH2 safety control relays with permanently mounted auxiliary contact blocks
Product Category IEC