Submittal Sheet

● at 600 V rated value
11A
Yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value
0.5hp
— at 230 V rated value
2hp
● for three-phase AC motor
— at 200/208 V rated value
3hp
— at 220/230 V rated value
3hp
— at 460/480 V rated value
7.5hp
— at 575/600 V rated value
10hp
Contact rating of auxiliary contacts according to UL A600 / Q600
Short-circuit protection
Design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required
gG NH 3NA, DIAZED 5SB, NEOZED 5SE: 50 A
— with type of assignment 2 required
gG NH 3NA, DIAZED 5SB, NEOZED 5SE: 25 A
● for short-circuit protection of the auxiliary switch
required
fuse gG: 10 A
Installation/ mounting/ dimensions
Mounting position +/-180° rotation possible on vertical mounting surface; can be
tilted forward and backward by +/- 22.5° on vertical mounting
surface
Mounting type screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
● Side-by-side mounting
Yes
Height 58mm
Width 45mm
Depth 73mm
Required spacing
● for grounded parts
— at the side
6mm
● for live parts
— at the side
6mm
Connections/Terminals
Type of electrical connection
● for main current circuit
screw-type terminals
● for auxiliary and control current circuit
screw-type terminals
Type of connectable conductor cross-sections
● for main contacts
— solid
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
— single or multi-stranded
2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), 2x 4 mm²
3RT2017-1AK62 Subject to change without notice