Submittal Sheet

● at 60 Hz
0.24
Closing delay
● at AC
8...33ms
Opening delay
● at AC
4...15ms
Arcing time 10...15ms
Control version of the switch operating mechanism Standard A1 - A2
Residual current of the electronics for control with
signal <0>
● at AC at 230 V maximum permissible
4mA
● at DC at 24 V maximum permissible
10mA
Auxiliary circuit
Number of NC contacts
● for auxiliary contacts
— instantaneous contact
1
Operating current at AC-12 maximum 10A
Operating current at AC-15
● at 230 V rated value
10A
● at 400 V rated value
3A
● at 500 V rated value
2A
● at 690 V rated value
1A
Operating current at DC-12
● at 24 V rated value
10A
● at 48 V rated value
6A
● at 60 V rated value
6A
● at 110 V rated value
3A
● at 125 V rated value
2A
● at 220 V rated value
1A
● at 600 V rated value
0.15A
Operating current at DC-13
● at 24 V rated value
10A
● at 48 V rated value
2A
● at 60 V rated value
2A
● at 110 V rated value
1A
● at 125 V rated value
0.9A
● at 220 V rated value
0.3A
● at 600 V rated value
0.1A
Contact reliability of auxiliary contacts 1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings
Full-load current (FLA) for three-phase AC motor
● at 480 V rated value
11A
3RT2017-1AK62 Subject to change without notice
Page 5/
11
11/29/2017 © Copyright Siemens