Submittal Sheet
— at 690 V at 60 °C rated value
22kW
● at AC-2 at 400 V rated value
5.5kW
● at AC-3
— at 230 V rated value
3kW
— at 400 V rated value
5.5kW
— at 500 V rated value
5.5kW
— at 690 V rated value
5.5kW
Operating power for approx. 200000 operating cycles
at AC-4
● at 400 V rated value
2kW
● at 690 V rated value
2.5kW
Thermal short-time current limited to 10 s 90A
Power loss [W] at AC-3 at 400 V for rated value of
the operating current per conductor
1.2W
No-load switching frequency
● at AC
100001/h
Operating frequency
● at AC-1 maximum
10001/h
● at AC-2 maximum
7501/h
● at AC-3 maximum
7501/h
● at AC-4 maximum
2501/h
Control circuit/ Control
Type of voltage of the control supply voltage AC
Control supply voltage at AC
● at 50 Hz rated value
110V
● at 60 Hz rated value
120V
Operating range factor control supply voltage rated
value of magnet coil at AC
● at 50 Hz
0.8...1.1
● at 60 Hz
0.8...1.1
Apparent pick-up power of magnet coil at AC
● at 50 Hz
36V·A
● at 60 Hz
36V·A
Inductive power factor with closing power of the coil
● at 50 Hz
0.8
● at 60 Hz
0.8
Apparent holding power of magnet coil at AC
● at 50 Hz
5.9V·A
● at 60 Hz
5.9V·A
Inductive power factor with the holding power of the
coil
● at 50 Hz
0.24
3RT2017-1AK62 Subject to change without notice
Page 4/
11
11/29/2017 © Copyright Siemens