Submittal Sheet
Number of CO contacts
● for auxiliary contacts
0
Operating current of auxiliary contacts at AC-15
● at 24 V
4A
● at 110 V
4A
● at 120 V
4A
● at 125 V
4A
● at 230 V
3A
Operating current of auxiliary contacts at DC-13
● at 24 V
2A
● at 60 V
0.55A
● at 110 V
0.3A
● at 125 V
0.3A
● at 220 V
0.11A
Protective and monitoring functions
Trip class CLASS 10E
Design of the overload release electronic
UL/CSA ratings
Full-load current (FLA) for three-phase AC motor
● at 480 V rated value
25A
● at 600 V rated value
25A
Contact rating of auxiliary contacts according to UL B600 / R300
Short-circuit protection
Design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required
gG: 125 A, RK5: 100A
— with type of assignment 2 required
gG: 63 A, J: 100A
● for short-circuit protection of the auxiliary switch
required
fuse gG: 6 A
Installation/ mounting/ dimensions
Mounting position any
Mounting type direct mounting
Height 87mm
Width 45mm
Depth 84mm
Required spacing
● with side-by-side mounting
— forwards
0mm
— Backwards
0mm
— upwards
0mm
— downwards
0mm
3RB3026-1QB0 Subject to change without notice