Submittal Sheet

Adjustable pick-up value current of the current-
dependent overload release
10...40A
Trip time at phase-loss maximum 3s
Relative repeat accuracy 1%
Product feature Protective coating on printed-circuit
board
Yes
Number of NC contacts of auxiliary contacts of
overload relay
1
Number of NO contacts of auxiliary contacts of
overload relay
1
Operating current of auxiliary contacts of overload
relay
● at AC at 600 V
5A
● at DC at 250 V
1A
Contact rating of auxiliary contacts of overload relay
according to UL
5A@600VAC (B600), 1A@250VDC (R300)
Insulation voltage
● with single-phase operation at AC rated value
600V
● with multi-phase operation at AC rated value
300V
Enclosure
Degree of protection NEMA rating of the enclosure NEMA 1
Design of the housing Indoor general purpose use
Mounting/wiring
Mounting position Vertical
Mounting type Surface mounting and installation
Type of electrical connection for supply voltage line-
side
Screw-type terminals
Tightening torque [lbf·in] for supply 35...35lbf·in
Type of connectable conductor cross-sections at line-
side at AWG conductors single or multi-stranded
1x(14 - 2 AWG)
Temperature of the conductor for supply maximum
permissible
75°C
Material of the conductor for supply AL or CU
Type of electrical connection for load-side outgoing
feeder
Screw-type terminals
Tightening torque [lbf·in] for load-side outgoing
feeder
35...35lbf·in
Type of connectable conductor cross-sections at
AWG conductors for load-side outgoing feeder single
or multi-stranded
1x(14 - 2 AWG)
Temperature of the conductor for load-side outgoing
feeder maximum permissible
75°C
Material of the conductor for load-side outgoing
feeder
AL or CU
Type of electrical connection of magnet coil screw-type terminals
US2:14DUE32BA Subject to change without notice
Page 3/
6
10/23/2017 © Copyright Siemens